5.3
Warning and error messages
Warning messages and error messages inform you of potentially critical operating states. EPP9022 signals
warning messages and error messages in two ways:
•
•
There are two categories of messages:
• A
warning message
is output if a measured value (current, voltage) is borderline. However, continuous
operation is still possible under unchanged conditions.
• An
error message
is output if continuous operation under unchanged conditions could lead to a defect
or to the tripping of a safety device.
The following diagrams show the threshold values for warning messages and error messages in the factory
setting.
Threshold values for supply voltages (factory setting)
Nominal voltage range
Warning
Error
Undervoltage
Overvoltage
8000:11
8010:11
"Voltage min
error limit"
"Voltage min
warning limit"
8000:15
8010:15
"Voltage max
warning limit"
"Voltage max
error limit"
8000:14
8010:14
8000:12
8010:12
Warning message
Warning message
Error message
Error message
Threshold values for output currents (factory setting)
Nominal current range
8000:16
8010:16
8000:13
8010:13
0 mA
"Current max
warning limit"
"Current max
error limit"
Overcurrent
Warning message
Error message