EPM Inputs Channel 2
Status
The status bits indicate
:
•
Voltage min error
Error message in case of undervoltage.
This bit is TRUE if the supply voltage U
P
is lower than CoE index
8010:11 "Voltage min error limit" (unit: mV).
Requirement: CoE index 8010:02 "Enable voltage min error" is
TRUE.
•
Voltage max error
Error message in case of overvoltage.
This bit is TRUE if the supply voltage U
P
is higher than CoE index
8010:12 "Voltage max error limit" (unit: mV).
Requirement: CoE index 8010:03 "Enable voltage max error" is
TRUE.
•
Current max error
Error message in case of overcurrent.
This bit is TRUE if the output current I
P
is higher than CoE index
8010:13 "Current max error limit" (unit: mA).
Requirement: CoE index 8010:04 "Enable current max Error" is
TRUE (default).
•
Voltage min warning
Warning message in case of undervoltage.
This bit is TRUE if the supply voltage U
P
is lower than CoE index
8010:14 "Voltage min warning limit" (unit: mV).
Requirement: CoE index 8010:05 "Enable voltage min warning" is
TRUE (default).
•
Voltage max warning
Warning message in case of overvoltage.
This bit is TRUE if the supply voltage U
P
is higher than CoE index
8010:15 "Voltage max warning limit" (unit: mV).
Requirement: CoE index 8010:06 "Enable voltage max warning" is
TRUE (default).
•
Current max warning
Warning message in case of overcurrent.
This bit is TRUE if the output current I
P
is higher than CoE index
8010:16 "Current max warning limit" (unit: mV).
Requirement: CoE index 8010:07 "Enable current max warning" is
TRUE (default).
•
Channel error
This bit is TRUE if at least one status bit of "EPM Inputs Channel
2" that signals an error message is TRUE:
Voltage min error
Voltage max error
Current max error
•
Channel warning
This bit is TRUE if at least one Status bit of "EPM Inputs Channel
2" that signals a warning message is TRUE:
Voltage min warning
Voltage max warning
Current max warning
•
TxPDO State
This bit is TRUE if an internal error occurs. The current
of "EPM Inputs Channel 2" are invalid if this bit is
TRUE.
•
TxPDO Toggle
This bit is inverted on each update of the
.
Summary of Contents for EPP9022-0060