Commissioning and configuration
EPP9022-0060
33
Version: 1.3
5.3.2
Disabling messages
NOTE
Critical operating states may not be reported under certain circumstances.
If you disable warning messages or error messages, EPP9022 will no longer inform you of critical operating
states:
overcurrent, overvoltage, undervoltage.
• Disable warning messages or error messages only if you have good reasons to do so.
You can disable the corresponding warning message/error message for each threshold value. All warning
messages and error messages are enabled in the factory setting.
To disable a warning message or error message, search for the CoE parameter for the desired message in
the tables below and set it to FALSE:
Input channel 1: Control voltage U
S
Reason for
message
Type of message
CoE parameter for enabling/
disabling the message
Undervoltage
Warning message
8000:05 "Enable voltage min warning"
Error message
8000:02 "Enable voltage min error"
Overvoltage
Warning message
8000:06 "Enable voltage max warning"
Error message
8000:03 "Enable voltage max error"
Overcurrent
Warning message
8000:07 "Enable current max warning"
Error message
8000:04 "Enable current max error"
Input channel 2: Peripheral voltage U
P
Reason for
message
Type of message
CoE parameter for enabling/
disabling the message
Undervoltage
Warning message
8010:05 "Enable voltage min warning"
Error message
8010:02 "Enable voltage min error"
Overvoltage
Warning message
8010:06 "Enable voltage max warning"
Error message
8010:03 "Enable voltage max error"
Overcurrent
Warning message
8010:07 "Enable current max warning"
Error message
8010:04 "Enable current max error"