Product overview
EP9224-0037
11
Version: 1.0
2.3
Technical data
Technical data
EP9224-0037
Fieldbus
Fieldbus
EtherCAT
Fieldbus connection
ENP B17 – connector
Electrical isolation
500 V (electrical isolation between EtherCAT cables and supply
voltages)
Supply
Nominal voltage
24 V
DC
(-15 % / +20 %)
Connections
Supply (X70): Connector B17 5G 1.5 mm² ENP
Downstream connection (X71): Socket B17 5G 1.5 mm² ENP
Connections, current carrying
capacity
max. 15.5 A per U
S
/U
P
to 45 °C
Supply of the module electronics
from the control voltage U
S
Current consumption of the
module electronics
typically 110 mA from U
S
,
typically 40 mA from U
P
Outputs
Fieldbus
EtherCAT P
Number of outputs
4
Connections
M8 sockets, p-coded, shielded
Nominal current
3 A per U
S
and U
P
on each EtherCAT P port
Nominal current (sum)
12 A per U
S
and U
P
Capacitive load C
Load
max. 2200 µF per U
S
and U
P
on each EtherCAT P port
Switch-on time delay
1)
:
„Fast“ = 10 ms
„Moderate“ = 100 ms (default)
„Slow“ = 200 ms
Overcurrent protection
Nominal current I
n
:
1 A .. 3 A per U
S
and U
P
on each EtherCAT P port.
Tripping characteristic
. Default 100 ms at 3 x I
n
.
Current limitation I
Lim
5 A per U
S
and U
P
on each EtherCAT P port.
Current limitation:
Switch-off time t
Lim
typically 75 ms
Fuse
Rated current: 5 A
Melting integral I²t: 5.566 A² s. (with a pulse width of 8 ms)
Further protective functions and diagnosis
Overtemperature protection:
Threshold values
T
warn
= 75 °C → warning on exceeding
T
err
= 85 °C → error message on exceeding
Undervoltage protection:
Threshold values
U
warn
= 21.6 V → warning on falling below
U
err
= 19.1 V → error message on falling below
Data logger: Sampling interval
:
1 ms
10 ms (default)
25 ms
100 ms
1000 ms
Data logger: Buffer size
25 entries.
1)
The output voltages are switched on one after the other at the start so that the starting currents do not add