Index 8000: RTD Settings Ch.1
Index (hex) Name
Meaning
Data type
Flags
Default
8000:0
RTD Settings Ch.1
Maximum subindex
UINT8
RO
0x1B (27
dec
)
8000:01
Enable user scale
Activates user scaling
BOOLEAN
RW
0x00 (0
dec
)
8000:02
Presentation
Presentation of the measured value
BIT3
RW
0x00 (0
dec
)
0
Signed, in two's complement
1
Most significant bit as sign
2
High-resolution (1/100 °C steps)
8000:05
Siemens bits
The S5 bits are displayed in the three low-order bits
BOOLEAN
RW
0x00 (0
dec
)
8000:06
Enable filter
Enable filter, which makes PLC-cycle-synchronous data
exchange unnecessary
BOOLEAN
RW
0x00 (0
dec
)
8000:07
Enable limit 1
Activates limit check for limit 1
BOOLEAN
RW
0x00 (0
dec
)
8000:08
Enable limit 2
Activates limit check for limit 2
BOOLEAN
RW
0x00 (0
dec
)
8000:0A
Enable user calibra-
tion
Activates user calibration
BOOLEAN
RW
0x00 (0
dec
)
8000:0B
Enable vendor cali-
bration
Activates vendor calibration
BOOLEAN
RW
0x01 (1
dec
)
8000:0E
Swap limit bits
Swaps the two limit bits, in order to achieve compatibility
with older hardware versions.
BOOLEAN
RW
0x00 (0
dec
)
8000:11
User scale offset
User scaling offset
INT16
RW
0x0000 (0
dec
)
8000:12
User scale gain
Gain of the user scaling
INT32
RW
0x00010000
(65536
dec
)
8000:13
Limit 1
Value for limit 1
INT16
RW
0x0000 (0
dec
)
8000:14
Limit 2
Value for limit 2
INT16
RW
0x0000 (0
dec
)
8000:15
Filter settings
Filter settings
UINT16
RW
0x0000 (0
dec
)
0
50 Hz
1
60 Hz
2
100 Hz
3
500 Hz
4
1 kHz
5
2 kHz
6
3.75 kHz
7
7.5 kHz
8
15 kHz
9
30 kHz
10
5 Hz
11
10 Hz
8000:16
Calibration interval
reserved
UINT16
RW
0x0000 (0
dec
)
8000:17
User calibration offset User calibration offset
INT16
RW
0x0000 (0
dec
)
8000:18
User calibration gain
Gain of the user calibration
UINT16
RW
0x4000
(16384
dec
)
8000:19
RTD element
Sensor type
UINT16
RW
0x0000 (0
dec
)
0
PT100
1
Ni100
2
PT1000
3
PT500
4
PT200
5
Ni1000
6
Ni1000 (Siemens)
7
Ni120
8
Resistance measurement with 1/16 ohm resolution
9
Resistance measurement with 1/64 ohm resolution