Commissioning
EL3182
95
Version: 1.2
Index
(hex)
Name
Meaning
Data type
Flags Default
1C32:0
SM output
parameter
Synchronization parameters for the
outputs
UINT8
RO
0x20 (32
dez
)
1C32:01
Sync mode
Current synchronization mode:
• 0: Free Run
• 1: Synchron with SM 2 Event
• 2: DC-Mode - Synchron with SYNC0
Event
• 3: DC-Mode - Synchron with SYNC1
Event
UINT16
RW
0x0001 (1
dez
)
1C32:02
Cycle time
Cycle time (in ns):
• Free Run: Cycle time of the local
timer
• Synchron with SM 2 Event: Master
cycle time
• DC mode: SYNC0/SYNC1 Cycle
Time
UINT32
RW
0x000F4240
(1000000
dez
)
1C32:03
Shift time
Time between SYNC0 event and
output of the outputs (in ns, DC mode
only)
UINT32
RO
0x00000000
(0
dez
)
1C32:04
Sync modes
supported
Supported synchronization modes:
• Bit 0 = 1: free run is supported
• Bit 1 = 1: Synchron with SM 2 event
is supported
• Bit 2-3 = 01: DC mode is supported
• Bit 4-5 = 10: Output shift with
SYNC1 event (only DC mode)
• Bit 14 = 1: dynamic times
(measurement through writing of
0x1C32:08)
UINT16
RO
0x4003
(16387
dez
)
1C32:05
Minimum cycle
time
Minimum cycle time (in ns)
UINT32
RO
0x0000FDE8
(65000
dez
)
1C32:06
Calc and copy
time
Minimale Zeit zwischen SYNC0 und
SYNC1 Event (in ns, nur DC-Mode)
UINT32
RO
0x00000000
(0
dez
)
1C32:07
Minimum delay
time
UINT32
RO
0x00000000
(0
dez
)
1C32:08
Command
• 0: Measurement of the local cycle
time is stopped
• 1: Measurement of the local cycle
time is started
• 0x1C32:03, 0x1C32:05, 0x1C32:06,
0x1C32:09,
0x1C33:06,
updated with the maximum
measured values. For a subsequent
measurement the measured values
are reset
UINT16
RW
0x0000 (0
dez
)
1C32:09
Maximum delay
time
Time between SYNC1 event and
output of the outputs (in ns, DC mode
only)
UINT32
RO
0x00000000
(0
dez
)
1C32:0B
SM event missed
counter
Number of missed SM events in
OPERATIONAL (DC mode only)
UINT16
RO
0x0000 (0
dez
)