Commissioning
EL3182
106
Version: 1.2
Fig. 108: Relationship of operating modes
The terminal switches between the Freerun (filter on) and Synchron modes by activating/deactivating the
filter via the index. The terminal remains in OP mode during this process. The changeover may result in
longer sampling times and step changes in the process data until the filters have assumed a steady state.
DC mode can only be used when the filters are switched off. Likewise, it is not possible to switch the filters
on in DC mode. The DC mode is parameterized via the DC tab in the TwinCAT System Manager.