HART
EL3182
120
Version: 1.2
The values are automatically updated every three seconds. This value is independent of the set polling time.
Cyclic process data
Furthermore, HART Cmd 3 can be mapped cyclically (see CoE object index
index 0x6090 for channel 2). A HART-specific set of additional process data, which can be read by the
control system, can be created by ticking the “Cyclic Process Data” checkbox.
Fig. 120: Additional PDO (Cmd 3) of the HART communication
Once the configuration has been activated, it is updated cyclically with the polling time used as time base.
The acyclic service from this dialog takes values from the cyclic buffer every three seconds.
6.4
Acyclic services
Simple reading or writing of individual HART commands can be initiated via the "Acyclic Services" dialog.