Commissioning
EL1502, EL1512
130
Version: 3.5
Index 8000 CNT Settings Ch.1
Index (hex) Name
Meaning
Data type
Flags
Default
8000:0
CNT Settings Ch.1
Maximum subindex
UINT8
RO
0x13 (19
dec
)
8000:01
Enable function to set
output
Activates the function for setting Output 1
BOOLEAN
RW
0x00 (0
dec
)
8000:02
Enable function to re-
set output
Activates the function for resetting Output 1
BOOLEAN
RW
0x00 (0
dec
)
8000:03
Enable reload
The counter counts to the value in index
0x8000:13
[
}
130]
BOOLEAN
RW
0x00 (0
dec
)
8000:04
Count down [
}
115]
Counting direction:
• 0: Up
• 1: Down
BOOLEAN
RW
0x00 (0
dec
)
8000:11
Switch on threshold
value
Switch-on threshold value for Output 1
UINT32
RW
0x00000000
(0
dec
)
8000:12
Switch off threshold
value
Switch-off threshold value for Output 1
UINT32
RW
0x00000000
(0
dec
)
8000:13
Counter reload value
The limit that can be activated via "Enable reload" (in-
dex
0x8000:03 [
}
130]
).
The counter counts to this limit and, on exceeding it,
begins again at zero.
UINT32
RW
0x00000001
(1
dec
)
Index 8010 CNT Settings Ch.2
Index (hex) Name
Meaning
Data type
Flags
Default
8010:0
CNT Settings Ch.2
Maximum subindex
UINT8
RO
0x13 (19
dec
)
8010:01
Enable function to set
output
Activates the function for setting Output 2
BOOLEAN
RW
0x00 (0
dec
)
8010:02
Enable function to re-
set output
Activates the function for resetting Output 2
BOOLEAN
RW
0x00 (0
dec
)
8010:03
Enable reload
The counter counts to the value in index
0x8010:13
[
}
130]
BOOLEAN
RW
0x00 (0
dec
)
8010:04
Count down [
}
115]
Counting direction
• 0: Up
• 1: Down
BOOLEAN
RW
0x00 (0
dec
)
8010:11
Switch on threshold
value
Switch-on threshold value for Output 2
UINT32
RW
0x00000000
(0
dec
)
8010:12
Switch off threshold
value
Switch-off threshold value for Output 2
UINT32
RW
0x00000000
(0
dec
)
8010:13
Counter reload value
The limit that can be activated via "Enable reload" (in-
dex
0x8010:03 [
}
130]
).
The counter counts to this limit and, on exceeding it,
begins again at zero.
UINT32
RW
0x00000001
(1
dec
)