Commissioning
EJ6002
44
Version: 1.5
6.2.4
Output data
Index 0x70n0 COM Outputs Ch. 1 (n = 0), Ch. 2 (n = 1)
Index
(hex)
Name
Meaning
Data type
Flags Default
70n0:0
COM Outputs Ch. 1 + Ch.
2
Max. SubIndex (hex)
UINT8
RO
0x26
(38
dec
)
70n0:01 Transmit request
By changing the state of this bit, the controller informs the module
that the DataOut bytes contain the number of bytes displayed in in-
dex 0x70n0:099 “Output length”.
The module acknowledges receipt of the data by changing the
state of the index 0x60n0:01 “
” bit.
Only now new data can be transferred from the controller to the
module.
BOOLEAN
RO
0x00
(0
dec
)
70n0:02 Receive accepted
The controller acknowledges receipt of data by changing the state
of this bit.
Only then new data can be transferred from the terminal to the con-
troller.
BOOLEAN
RO
0x00
(0
dec
)
70n0:03 Init request
0:
The controller once again requests the module to prepare for serial
data exchange.
1:
The controller requests the module for initialization.
The transmit and receive functions will be blocked
The FIFO pointer will be reset and the interface will be initialized
with the values of the responsible Settings object. The execution of
the initialization will be acknowledged by the module with the “
BOOLEAN
RO
0x00
(0
dec
)
70n0:04 Send continuous
Continuous sending of data from the FIFO.
The send buffer is filled (up to 128 bytes) by the controller. The
filled buffer contents will be sent on the rising edge of the bit.
If the data has been transmitted, the module informs the controller
by setting the “
” bit in index 0x60n0:03. “Init ac-
cepted” is cleared with “Send continuous”.
BOOLEAN
RO
0x00
(0
dec
)
70n0:09 Output length
Number of output bytes available for transfer from the controller to
the module.
UINT8
RO
0x00
(0
dec
)
70n0:11 Data Out 0
Output byte 0
UINT8
RO
0x00
(0
dec
)
...
...
....
...
...
...
70n0:26 Data Out 21
Output byte 21
UINT8
RO
0x00
(0
dec
)
Index 0x70n1 COM Ext. Outputs Ch. 1 (n = 0), Ch. 2 (n = 1)
Index
(hex)
Name
Meaning
Data type
Flags Default
70n1:0
COM Ext. Outputs Ch. 1 +
Ch. 2
Max. SubIndex (hex)
UINT8
RO
0x02
(2
dec
)
70n1:01 Tx
Transmit signal
In operation mode
“RS232, manual operation” (CoE
= 17
dec
) the level
of Tx output can be set manually here.
Sending and receiving data is not handled by the firmware in this
operation mode.
BOOLEAN
RO
0x00
(0
dec
)
70n1:02 RTS
Request to send signal
In operation mode
“RS232, manual operation” (CoE
= 17
dec
) or
“RS232, manual flow control” (CoE
= 18
dec
) the
level of RTS output can be set manually here.
Sending and receiving data is not handled by the firmware in
“RS232, manual operation” mode.
BOOLEAN
RO
0x00
(0
dec
)