Commissioning

EJ6002

56

Version: 1.5

Index 1C33 SM input parameter

Index
(hex)

Name

Meaning

Data type

Flags Default

1C33:0

SM input parameter

Synchronization parameters for the inputs

UINT8

RO

0x20 (32

dec

)

1C33:01

Sync mode

Current synchronization mode:

• 0: Free Run

• 1: Synchron with SM 3 Event (no outputs available)

• 2: DC - Synchron with SYNC0 Event

• 3: DC - Synchron with SYNC1 Event

• 34: Synchron with SM 2 Event (outputs available)

UINT16

RW

0x0022 (34

dec

)

1C33:02

Cycle time

Cycle time (in ns):

• Free Run: Cycle time of the local timer

• Synchron with SM 2 Event: Master cycle time

• DC mode: SYNC0/SYNC1 Cycle Time

UINT32

RW

0x0003D090
(250000

dec

)

1C33:03

Shift time

Time between SYNC0 event and reading of the inputs (in
ns, only DC mode)

UINT32

RO

0x00000384
(900

dec

)

1C33:04

Sync modes supported

Supported synchronization modes:

• Bit 0: free run is supported

• Bit 1: Synchron with SM 2 Event is supported

(outputs available)

• Bit 1: Synchron with SM 3 Event is supported (no

outputs available)

• Bit 2-3 = 01: DC mode is supported

• Bit 4-5 = 01: Input Shift through local event (outputs

available)

• Bit 4-5 = 10: Input Shift with SYNC1 Event (no

outputs available)

• Bit 14 = 1: dynamic times (measurement through

writing of 0x1C33:08)

UINT16

RO

0x0001 (1

dec

)

1C33:05

Minimum cycle time

Minimum cycle time (in ns)

UINT32

RO

0x00002710
(10000

dec

)

1C33:06

Calc and copy time

Time between reading of the inputs and availability of the
inputs for the master (in ns, only DC mode)

UINT32

RO

0x00000000 (0

dec

)

1C33:07

Minimum delay time

Min. time between SYNC1 event and the reading of the
inputs (in ns, DC mode only)

UINT32

RO

0x00000384
(900

dec

)

1C33:08

Command

With this entry the real required process data provision
time can be measured.

• 0: Measurement of the local cycle time is stopped

• 1: Measurement of the local cycle time is started

The entries 0x1C33:03, 0x1C33:06, 0x1C33:09 are up-
dated with the maximum measured values.
For a subsequent measurement the measured values
are reset

UINT16

RW

0x0000 (0

dec

)

1C33:09

Maximum Delay time

Time between SYNC1 event and reading of the inputs (in
ns, only DC mode)

UINT32

RO

0x00000384
(900

dec

)

1C33:0B

SM event missed
counter

Number of missed SM events in OPERATIONAL (DC
mode only)

UINT16

RO

0x0000 (0

dec

)

1C33:0C

Cycle exceeded counter Number of occasions the cycle time was exceeded in

OPERATIONAL (cycle was not completed in time or the
next cycle began too early)

UINT16

RO

0x0000 (0

dec

)

1C33:0D

Shift too short counter

Number of occasions that the interval between SYNC0
and SYNC1 event was too short (DC mode only)

UINT16

RO

0x0000 (0

dec

)

1C33:20

Sync error

The synchronization was not correct in the last cycle
(outputs were output too late; DC mode only)

BOOLEAN

RO

0x00 (0

dec

)

Summary of Contents for EJ6002

Page 1: ...Documentation EN EJ6002 2 channel serial interface RS232 RS422 or RS485 2022 06 23 Version 1 5...

Page 2: ......

Page 3: ...pply for the EtherCAT plug in modules 23 4 2 EJxxxx dimensions 25 4 3 Installation positions and minimum distances 26 4 3 1 Minimum distances for ensuring installability 26 4 3 2 Installation position...

Page 4: ...of contents EJ6002 4 Version 1 5 6 2 4 Output data 44 6 2 5 Information and diagnostic data 45 6 2 6 Standard objects 0x1000 0x1FFF 45 6 2 7 Command object 0xFB00 57 7 Appendix 58 7 1 Support and Serv...

Page 5: ...ducts that have already been supplied may be made on the basis of the data diagrams and descriptions in this documentation Trademarks Beckhoff TwinCAT TwinCAT BSD TC BSD EtherCAT EtherCAT G EtherCAT G...

Page 6: ...ined specialists in control automation and drive engineering who are familiar with the applicable national standards Description of instructions In this documentation the following instructions are us...

Page 7: ...ct description and parameterization 1 4 Update chapter Marking of EtherCAT plug in modules Update Technical Data Chapter Disposal added Update structure 1 3 Update chapter Configuration data 1 2 New t...

Page 8: ...of EtherCAT Components 2 Infrastructure for EtherCAT Ethernet Technical recommendations and notes for design implementation an testing 3 Design Guide EJ8xxx Signal distribution board for standard Ethe...

Page 9: ...herCAT plug in modules s following illustration A and B Fig 1 Order identifier A Revision number B and serial number C using the example of EJ1008 Product group Example Product designation Version Rev...

Page 10: ...L file which is available for download from the Beckhoff web site The product designation version and revision are read as decimal numbers even if they are technically saved in hexadecimal Serial numb...

Page 11: ...roduct it can be found in the following places on the packaging unit directly on the product if space suffices on the packaging unit and the product The BIC is machine readable and contains informatio...

Page 12: ...composite information from items 1 4 and with the above given example value on positon 6 The data identifiers are marked in bold font for better display 1P072222SBTNk4p562d71KEL1809 Q1 51S678294 Accor...

Page 13: ...uced into the Beckhoff I O production terminals box modules from 2020 widespread implementation is expected in 2021 The user can electronically access the eBIC if existent as follows With all EtherCAT...

Page 14: ...cific content is stored with the help of a category according to ETG 2010 ID 03 indicates to all EtherCAT masters that they must not overwrite these data in case of an update or restore the data after...

Page 15: ...n the side of the modules The cRUus imprint identifies devices that meet product safety requirements according to U S and Canadian regulations The warning symbol is a request to read the corresponding...

Page 16: ...lication specific plug connectors in order to connect the controller to further machine modules Using pre assembled cable harnesses avoids the need for time consuming connection of individual wires Co...

Page 17: ...RS232 RS422 and RS485 baud rates and modes e g termination BIAS failsafe can be configured via software The devices connected to the EJ6002 EtherCAT plug in module communicate with the automation dev...

Page 18: ...on signal distribution board Pollution degree 2 Mounting position Standard 27 Position of the coding pins 30 2 and 5 Color coding grey Vibration shock resistance according to EN 60068 2 6 EN 60068 2...

Page 19: ...8 EJ6002 Pinout RS232 The PCB footprint can be downloaded from the Beckhoff homepage NOTE Damage to devices possible The pins named with NC must not be connected Before installation and commissioning...

Page 20: ...9 EJ6002 Pinout RS422 The PCB footprint can be downloaded from the Beckhoff homepage NOTE Damage to devices possible The pins named with NC must not be connected Before installation and commissioning...

Page 21: ...10 EJ6002 Pinout RS485 The PCB footprint can be downloaded from the Beckhoff homepage NOTE Damage to devices possible The pins named with NC must not be connected Before installation and commissioning...

Page 22: ...c Manager channels and the distributed clocks Outputs remain in safe state on Operational State of the EtherCAT State Machine OP normal operating state mailbox and process data communication is possib...

Page 23: ...e found for each module in the respective documentation in section Technical data online and in the catalog The power requirement of the module string is displayed in the TwinCAT System Manager E bus...

Page 24: ...to 2 000 mA E bus current If a higher current is required due to the attached terminals power feed terminals or power supply plug in modules must be used for the E bus supply with a peripheral voltag...

Page 25: ...le type Dimensions W x H x D Sample in figure below Coupler 44 mm x 66 mm x 55 mm EJ1100 ej_44_2xrj45_coupler Single module 12 mm x 66 mm x 55 mm EJ1809 ej_12_16pin_code13 Double module 24 mm x 66 mm...

Page 26: ...ules Fig 16 Mounting distances EJ module PCB Observing the reaching area A minimum reaching area of 92 mm is required for assembly disassembly in order to be able to reach the mounting tabs with the f...

Page 27: ...sure that the specified conditions see Technical data are adhered to Optimum installation position standard For the optimum installation position the signal distribution board is installed horizontall...

Page 28: ...ll other installation positions are characterized by a different spatial position of the signal distribution board see Fig Other installation positions The minimum distances to ambient specified above...

Page 29: ...gram above The color code indicates the signal type The following table provides an overview of the signal types with corresponding color coding Signal type Modules Color Coupler EJ11xx No color codin...

Page 30: ...lation and service Couplers and placeholder modules have no coding pins Fig 20 Mechanical position coding with coding pins B1 and B2 and coding holes A1 and A2 The following diagram shows the position...

Page 31: ...of EJ modules A1 A2 Latching lugs top bottom C1 C2 Mounting holes B1 B2 Coding pins D1 D2 Coding holes To install the modules on the signal distribution board proceed as follows 1 Before the installat...

Page 32: ...g installation ensure safe latching of the modules on the signal distribution board The conse quences of inadequate contact pressure include loss of quality of the transferred signals increased power...

Page 33: ...uption in EtherCAT communication and must be equipped with placeholder modules In contrast to the passive terminals of the EL series the placeholder modules actively participate in the data exchange S...

Page 34: ...lation of EJ modules EJ6002 34 Version 1 5 4 6 2 Linking with EtherCAT Terminals and EtherCAT Box modules via an Ethernet EtherCAT connection Fig 24 Example of extension via an Ethernet EtherCAT conne...

Page 35: ...ied from the power supply unit of the Embedded PC The E bus signals and the supply voltage of the field side UP are routed directly to the PCB via a plug connector at the rear of the EtherCAT EJ coupl...

Page 36: ...optimally connected to the IPC via the corresponding EtherCAT Cable see following Fig A The IPC can be supplied directly via the signal distribution board using the enclosed power plug see Fig B belo...

Page 37: ...Disassembly of EJ modules To disassemble the module from the signal distribution board proceed as follows 1 Before disassembly ensure that the signal distribution board is securely connected to the m...

Page 38: ...EtherCAT basics EJ6002 38 Version 1 5 5 EtherCAT basics Please refer to the EtherCAT System Documentation for the EtherCAT fieldbus basics...

Page 39: ...rameterized via the CoE Online tab with a double click on the respec tive object or via the Process Data tab assignment of PDOs A detailed description can be found in the EtherCAT System Documentation...

Page 40: ...XOFF is not supported for input data TRUE XON XOFF is supported for input data BOOLEAN RW 0x00 0dec 80n0 04 Enable send FIFO data continuous FALSE No continuous sending of data from the FIFO TRUE Con...

Page 41: ...x00000010 16dec 16dec RS232 default Rx Tx RTS CTS are controlled automatically 17dec RS232 manual operation The input of Rx and CTS can be read from the ext status 0x60n1 43 The outputs Tx and RTS can...

Page 42: ...ec 64dec RS485 Busdevice This configuration will not enable the termination or the BIAS Failsafe resistors It is designed for devices which are connected in between of the two terminating devices 65de...

Page 43: ...by the module BOOLEAN RO 0x00 0dec 60n0 04 Buffer full The receive FIFO is full Note All incoming data will be lost from this point on BOOLEAN RO 0x00 0dec 60n0 05 Parity error A parity error has occu...

Page 44: ...dule with the Init accepted 43 bit in index 0x60n0 03 BOOLEAN RO 0x00 0dec 70n0 04 Send continuous Continuous sending of data from the FIFO The send buffer is filled up to 128 bytes by the controller...

Page 45: ...ta bytes in the receive FIFO UINT16 RO 0x0000 0dec Index F000 Modular device profile Index hex Name Meaning Data type Flags Default F000 0 Modular device profile General information for the modular de...

Page 46: ...ype Flags Default 1018 0 Identity Information for identifying the slave UINT8 RO 0x04 4dec 1018 01 Vendor ID Vendor ID of the EtherCAT slave UINT32 RO 0x00000002 2dec 1018 02 Product code Product code...

Page 47: ...COM Outputs Ch 1 entry 0x17 Data Out 6 UINT32 RO 0x7000 17 8 1600 0E SubIndex 014 14 PDO Mapping entry object 0x7000 COM Outputs Ch 1 entry 0x18 Data Out 7 UINT32 RO 0x7000 18 8 1600 0F SubIndex 015...

Page 48: ...uts Ch 1 PDO Mapping RxPDO 2 UINT8 RO 0x03 03dec 1601 01 SubIndex 001 1 PDO Mapping entry object 0x7001 COM Ext Out puts Ch 1 entry 0x01 Tx UINT32 RO 0x7001 01 1 1601 02 SubIndex 002 2 PDO Mapping ent...

Page 49: ...COM Outputs Ch 2 entry 0x17 Data Out 6 UINT32 RO 0x7010 17 8 1602 0E SubIndex 014 14 PDO Mapping entry object 0x7010 COM Outputs Ch 2 entry 0x18 Data Out 7 UINT32 RO 0x7010 18 8 1602 0F SubIndex 015...

Page 50: ...uts Ch 2 PDO Mapping RxPDO 4 UINT8 RO 0x03 03dec 1603 01 SubIndex 001 1 PDO Mapping entry object 0x7011 COM Ext Out puts Ch 2 entry 0x01 Tx UINT32 RO 0x7011 01 1 1603 02 SubIndex 002 2 PDO Mapping ent...

Page 51: ...5 8 1A00 0F SubIndex 015 15 PDO Mapping entry object 0x0x6000 COM Inputs Ch 1 entry 0x16 Data In 5 UINT32 RO 06000 16 8 1A00 10 SubIndex 016 16 PDO Mapping entry object 0x0x6000 COM Inputs Ch 1 entry...

Page 52: ...nputs Ch 1 PDO Mapping TxPDO 2 UINT8 RO 0x03 3dec 1A01 01 SubIndex 001 1 PDO Mapping entry object 0x6001 COM Ext Inputs Ch 1 entry 0x01 Rx UINT32 RO 0x6001 01 1 1A01 02 SubIndex 002 2 PDO Mapping entr...

Page 53: ...5 8 1A02 0F SubIndex 015 15 PDO Mapping entry object 0x0x6010 COM Inputs Ch 2 entry 0x16 Data In 5 UINT32 RO 06010 16 8 1A02 10 SubIndex 016 16 PDO Mapping entry object 0x0x6010 COM Inputs Ch 2 entry...

Page 54: ...pe Index hex Name Meaning Data type Flags Default 1C00 0 Sync manager type Using the Sync Managers UINT8 RO 0x04 4dec 1C00 01 SubIndex 001 Sync Manager Type Channel 1 Mailbox Write UINT8 RO 0x01 1dec...

Page 55: ...le time Minimum cycle time in ns UINT32 RO 0x00002710 10000dec 1C32 06 Calc and copy time Time between reading of the inputs and availability of the inputs for the master in ns only DC mode UINT32 RO...

Page 56: ...le time Minimum cycle time in ns UINT32 RO 0x00002710 10000dec 1C33 06 Calc and copy time Time between reading of the inputs and availability of the inputs for the master in ns only DC mode UINT32 RO...

Page 57: ...mands are available at this time OCTET STRING 16 bit RW FB00 02 Status Status of the command currently being executed 0 Command executed without error and without re sponse 1 Command executed without...

Page 58: ...nts there Beckhoff Support Support offers you comprehensive technical assistance helping you not only with the application of individual Beckhoff products but also with other wide ranging services sup...

Page 59: ......

Page 60: ...Beckhoff Automation GmbH Co KG H lshorstweg 20 33415 Verl Germany Phone 49 5246 9630 info beckhoff com www beckhoff com More Information www beckhoff com EJ6002...

Reviews: