Commissioning
EJ6002
42
Version: 1.5
Index
(hex)
Name
Meaning
Data type
Flags Default
80n0:1D
Mode of operation
35
dec
RS422, Terminated and BIAS/Failsafe RX (End-
device)
Point to point connection between two devices.
The termination resistor and the BIAS/Failsafe re-
sistors on the receiver are enabled.
This should be the default mode for a RS422 con-
figuration.
UINT32
RW
0x00000010
(16
dec
)
64
dec
RS485 (Busdevice)
This configuration will not enable the termination
or the BIAS/Failsafe resistors.
It is designed for devices which are connected in
between of the two terminating devices.
65
dec
RS485, Terminated
RS485 configuration with enabled termination re-
sistor
66
dec
RS485, BIAS/Failsafe
RS485 configuration with enabled termination re-
sistor
67
dec
RS485, Terminated and BIAS/Failsafe (Endde-
vice)
RS485 configuration with enabled termination re-
sistor and enabled BIAS/Failsafe resistors.
This should be the default configuration for both
endpoints of the RS485 network.