Product overview
BC3150
12
Version: 2.1.0
2.3.2
Technical data - PROFIBUS-DP
Fig. 2: BC3150
System data
PROFIBUS (BC3150)
Number of I/O modules
126 (BC3150 max. 99 devices)
Number of I/O points
depending on controller
Data transfer medium
shielded copper cable 2 x 0.25 mm², cable type A according to
EN 50 170
Segment length
up to 1200 m
Number of segments
3
Data transfer rate
up to 12 MBaud
Topology
RS485 line, optical fiber ring
Transmission time
approx. 0.5 ms with 10 stations for 32 bits input/output at 12 MBaud
2.3.3
Technical Data - PLC
PLC data
BCxx5x
Programmability
via serial programming interface or via the fieldbus
Program memory
48 kbyte
Source code memory
128 kbyte
Data memory
32 kbyte
Remanent flags
2 kbyte
PLC cycle time
Approx. 3.0 ms for 1000 IL commands (without I/O cycle)
Programming languages
IEC 6-1131-3 (IL, LD, FBD, ST, SFC)
Runtime
1 PLC task
Online Change
Yes
Up/Down Load Code
Yes/Yes