![Beck 14-100 Instruction Manual Download Page 54](http://html1.mh-extra.com/html/beck/14-100/14-100_instruction-manual_2718148054.webp)
54
80-1403-01, Rev. 3
Transducer Block Listing
Relative
Index
Record Name (if applicable):
Parameter Label
Use
1
ST_REV
fieldbus use, no Beck use
2
TAG_DESC
fieldbus use, no Beck use
3
STRATEGY
fieldbus use, no Beck use
4
ALERT_KEY
fieldbus use, no Beck use
5
MODE_BLK
typically Auto or CASCADE
6
BLOCK_ERR
fieldbus use
7
EVENT_UPDATE
fieldbus use
8
BLOCK_ALM
fieldbus use
9
TRANSDUCER_DIRECTORY
fieldbus use
10
TRANSDUCER_TYPE
fieldbus use
11
XD_ERROR
fieldbus use
12
COLLECTION_DIRECTORY
fieldbus use
13
Position %
present actuator position
14
Position Unit
unit of measure for Position %
15
Demand %
present actuator Demand
16
Demand Unit
unit of measure for Demand %
17
Op Mode
Demand Operating Mode
18
Trq/Thr %
present output shaft Torque load
19
Trq/Thr Unit
not used in Group 14
20
Ambient Temp
present DCM-3 temperature
21
Temp Unit
unit of measure for Ambient temperature
22-1
Inhibits: EXT 2 Inhibitor
not used in Group 14
22-2
Inhibits: EXT 1 Inhibitor
reason motor is not extending output shaft
22-3
Inhibits: RET 2 Inhibitor
not used in Group 14
22-4
Inhibits: RET 1 Inhibitor
Reason motor is not retracting output shaft
22-5
Inhibits: LED Status
allows remote checking of which LED’s on the DCM-3 are
illuminated
22-6
Inhibits: Switch Status
not used in Group 14
23-1
DCM BIST: Operating Status
summary of process-related conditions
23-2
DCM BIST: BIST 1
built-in self-test results
23-3
DCM BIST: BIST 2
built-in self-test results
23-4
DCM BIST: BIST 3
built-in self-test results
23-5
DCM BIST: analog_output_fixed1
not used in Group 14
23-6
DCM BIST: Analog Sig Saturated
analog signals are out of measurement range
24-1
SigDif: DemPosDiff Unit
unit of measure for DemPosDiff
24-2
SigDif: DemPosDiff
the difference between the Demand and the Position
25-1
Statistics: TotalRunTm
total amount of time the motor has been powered
25-2
Statistics: OverTrqs/Thrusts
not used in Group 14
25-3
Statistics: Peak Trq/Thr
not used in Group 14
25-4
Statistics: Reversals
the total number of times the motor has started in the
direction opposite to the previous start
25-5
Statistics: Stalls
the total number of times the stall timer has timed out
25-6
Statistics: Starts
the total number of motor starts
25-7
Statistics: LastRun
the duration of the last motor movement
25-8
Statistics: Set up OverTrqs/Thrusts not used in Group 14
25-9
Statistics: Set up OverTrqs/Thrusts not used in Group 14
FOUNDATION FIELDBUS
Transducer Block