6
3
2
+
-
12-24 V DC
COM
NC
COM
NC
X
ON
OFF
A
B
A
B
PZ1
4
*
*
WIRING
ORANGE
OFF
DIP-SWITCH ADJUSTMENTS
POWER SUPPLY
TEST
STOP IMPULSE
Opening side of the door
REOPENING IMPULSE
Closing side of the door
All wires must be connected. For compliance with EN 16005 and DIN 18650, the door controller test output
must be connected and able to test the sensor.
After changing a DIP-switch, the orange LED flashes. A LONG push on the
push button confirms the settings. Afterwards, a number of green flashes (x)
indicates the number of connected modules.
1 DOOR SIDE
2 ENVIRONMENT
3 BACKGROUND
4 PINCH ZONE
RELAY 1
STANDARD
CRITICAL
ON
OFF
ON
OFF
LED during detection:
R1 = RED
R2 = GREEN
RELAY 2
Adjust DIP 1 according to the door side on which the module is mounted.
Adjust the other DIP-settings only if needed.
Switch to CRITICAL when
external disturbances are likely
to cause unwanted detections
(min. obj size, immunity and
uncovered zone are increased).
Switch to OFF when there
is no background (glass
floor, footbridge...).
Switch to OFF when the hinge
area does not need to be
secured and objects can cause
unwanted detections.
ANGLE ADJUSTMENTS
Adjust the angle of the laser curtain
if needed.
Make sure that the standing testbody
is always detected.
GREEN
FACTORY VALUE
GREEN
BROWN
YELLOW
WHITE
PINK
GREY
RED
BLUE
Always launch a teach-in after changing the angle of the sensor.
In order to change these settings by remote control, adjust the corresponding DIP-switches to ON.
* Output status when sensor is operational.