4.6 Combustible Shelf
This appliance may be fitted below a surround with a combustible shelf providing the
following dimensional criteria is met:
There must be a minimum distance of 400mm from the top of the appliance to the underside
of the shelf.
The shelf must not project more than 150mm from the mounting surface of the appliance into
the room. If the shelf projects more than 150mm then the distance between the top of the
appliance and the underside of the shelf must be increased accordingly; for every 10mm of
projection above 150mm the distance between the fire and shelf must be increased by 25mm
Shelf Protrusion (X)
Min. Distance (Y) Between Fire and Shelf
150mm
400mm
160mm
425mm
170mm
450mm
180mm
475mm
190mm
500mm
200mm
525mm
Any combustible side wall, for example leg of timber mantel, should be a minimum of 200mm
from the appliance.