Thermostat Wiring
If you need to replace your thermostat wiring, or are installing wiring for new equipment, the
following wire specification must be followed to maintain the safety ratings of UL 873:
18 AWG 4, 5, or 7 Conductor 300V, Type CL2 (UL) 105 Deg C.
Control Module Terminals
Required by UL 873: the connector manufacturer specifies the connector terminal screws
should be torqued to 4.43 in-lbs (0.5 Nm).