Function
Prog.
no.
Level
1)
Standard value
Heating curve displacement
1021
E
0.0°C
Heating curve adaption
Off | On
1026
E
Off
Summer/winter heating limit
1030
Eu
20°C
24-hour heating limit
1032
E
0°C
Flow temp setpoint min
1040
E
8°C
Flow temp setpoint max
1041
E
80°C
Flow temp setpoint room stat
1042
E
- - -°C
Delayed heat request
1046
E
0 s
Room influence
1050
C
- - - %
Room temp limitation
1060
E
0.5°C
Boost heating
1070
E
- - -°C
Quick setback
Off | Down to reduced setpoint | Down to frost prot setpoint
1080
E
Down to reduced set-
point
Optimum start control max
1090
E
0 min
Optimum stop control max
1091
E
0 min
Reduced setp increase start
1100
E
- - -°C
Reduced setp increase end
1101
E
-15°C
Continuous pump operation
No | Yes
1109
E
No
Overtemp prot pump circuit
Off | On
1120
E
Off
Mixing valve boost
1130
E
5°C
Actuator running time
1134
E
120 s
Floor curing function
Off | Functional heating | Curing heating | Functional/curing heating |
Curing/Functional heating | Manually
1150
E
Off
Floor curing setp manually
1151
E
25°C
Floor curing setp current
1155
E
- - -°C
Floor curing day current
1156
E
0
Excess heat draw
Off | Heating mode | Always
1161
E
Heating mode
With buffer storage tank
No | Yes
1170
E
Yes
With prim contr/system pump
No | Yes
1172
E
Yes
Pump speed reduction
Operating level | Characteristic
1180
E
Characteristic
Pump speed min
1182
C
10 %
Pump speed max
1183
C
100 %
Curve readj at 50% speed
1188
E
10 %
Flow setp readj speed ctrl
No | Yes
1190
E
Yes
Operating level changeover
Frost protection | Reduced | Comfort
1198
E
Reduced
Programming
3
7
Summary of Contents for POWER HT-A 1.430
Page 1: ... 1 QVWDOODWLRQ PDQXDO DV FRQGHQVLQJ ERLOHUV 3RZHU 7 ...
Page 8: ......
Page 13: ...3 4 Wiring diagram Fig 3 Wiring diagram Technical Data 3 1 ...
Page 41: ...Connection diagram Prior to installation 1 4 ...
Page 43: ...Connection diagram Prior to installation 3 4 ...
Page 45: ...Connection diagram Prior to installation 5 4 ...
Page 47: ...Wiring plan right POWER HT A Prior to installation 47 ...
Page 48: ...Wiring plan left POWER HT A Prior to installation 48 ...
Page 49: ...4 17 Legend Prior to installation 9 4 ...
Page 161: ...Space for notes 1 6 1 ...
Page 162: ...Space for notes 2 6 1 ...
Page 163: ...Space for notes 3 6 1 ...
Page 164: ......