Water content of
the plant
[l]
Amount
Lasacor
®
LS 1
[l]
Water in the mixture
*)
[l]
Antifreeze to
[°C]
50
36
14
-15
100
71
29
-15
150
107
43
-15
200
143
57
-15
250
178
72
-15
300
214
86
-15
500
357
143
-15
1000
714
286
-15
*) The water for the mixture must be neutral (potable water quality with no more than 100 mg/kg chlorine) or
demineralised. Please also follow the manufacturer instructions.
Maintenance instruction
The water hardness of the heating water has to be checked within the scope of the
recommended maintenance of the boiler and, possibly, the respective amount of
additive has to be added.