Function
Prog.
no.
Level
1)
Standard value
Delayed heat request
746
E
0 s
Room influence
750
C
- - - %
Room temp limitation
760
E
0.5°C
Boost heating
770
E
- - -°C
Quick setback
Off | Down to reduced setpoint | Down to frost prot setpoint
780
E
Down to reduced set-
point
Optimum start control max
790
E
0 min
Optimum stop control max
791
E
0 min
Reduced setp increase start
800
E
- - -°C
Reduced setp increase end
801
E
15°C
Continuous pump operation
No | Yes
809
E
No
Overtemp prot pump circuit
Off | On
820
E
Off
Mixing valve boost
830
E
5°C
Actuator running time
834
E
120 s
Floor curing function
Off | Functional heating | Curing heating | Functional/curing heating |
Curing/Functional heating | Manually
850
E
Off
Floor curing setp manually
851
E
25°C
Floor curing setp current
855
E
- - -°C
Floor curing day current
856
E
0
Excess heat draw
Off | Heating mode | Always
861
E
Heating mode
With buffer storage tank
Off | Heating mode | Always
870
E
Yes
With prim contr/system pump
No | Yes
872
E
Yes
Pump speed reduction
Operating level | Characteristic
880
E
Characteristic
Pump speed min
882
C
10 %
Pump speed max
883
C
100 %
Curve readj at 50% speed
888
E
10 %
Flow setp readj speed ctrl
No | Yes
890
E
Yes
Operating level changeover
Frost protection | Reduced | Comfort
898
E
Reduced
Optg mode changeover
None | Protection | Reduced | Comfort | Automatic
900
E
Protection
Heating circuit 2
This parameter will only be visible if heating circuit 2 is installed.
Comfort setpoint
1010
Eu
20.0°C
Reduced setpoint
1012
Eu
18.0°C
Frost protection setpoint
1014
Eu
10.0°C
Heating curve slope
1020
Eu
1.50
Programming
2
7
Summary of Contents for POWER HT-A 1.430
Page 1: ... 1 QVWDOODWLRQ PDQXDO DV FRQGHQVLQJ ERLOHUV 3RZHU 7 ...
Page 8: ......
Page 13: ...3 4 Wiring diagram Fig 3 Wiring diagram Technical Data 3 1 ...
Page 41: ...Connection diagram Prior to installation 1 4 ...
Page 43: ...Connection diagram Prior to installation 3 4 ...
Page 45: ...Connection diagram Prior to installation 5 4 ...
Page 47: ...Wiring plan right POWER HT A Prior to installation 47 ...
Page 48: ...Wiring plan left POWER HT A Prior to installation 48 ...
Page 49: ...4 17 Legend Prior to installation 9 4 ...
Page 161: ...Space for notes 1 6 1 ...
Page 162: ...Space for notes 2 6 1 ...
Page 163: ...Space for notes 3 6 1 ...
Page 164: ......