By pressing on + or - on REG (R), the minimum air quantity of the blower is adjusted.
Possible settings are 10-20-30-40-50.
The factory setting is (- 20) = 20%
(
–
XX)
When the desired value is shown in the display, save by pressing button (C).
Here, the worm conveyor/auger's running-in time is adjusted at "high output" - i.e. the
time which the worm conveyor/auger is running each time. Adjustment area: 0.1-6.0
corresponding to 0.1-6.0 seconds.
(HX.X)
Save with button (C).
Here, the worm conveyor/auger's adjustment time is adjusted at "low output" - i.e. the
time which the worm conveyor/auger is running each time. Adjustment area: 0.1-6.0,
corresponding to 0.1-6.0 seconds.
(LX.X)
Factory setting::
MULTI-HEAT
Type
HX.X
(high output)
LX.X
(low output)
1,5
H1,7 = 1,7 sec.
L1,7 = 1,7 sec.
2,5
H0,5 = 0,5 sec.
L0,3 = 0,3 sec.
4,0
H1,0 = 1,0 sec.
L0,6 = 0,6 sec.
Here, the time which the blower is to run with maximum air quantity is adjusted when
the fuel worm conveyor/auger is in the interval situation.
(PXX)
(Possible setting: 0-10 seconds).