The lowest button is used to set the number of seconds between each worm conveyor/
auger delivery - this can be set between 10 and 60 seconds, but never below the setting
of the high output. The setting is shown in the display. Press in and hold "SEC" and
adjust up or down by means of pressing on + or
–
. Using the uppermost button, set the
blower's air quantity from 0 to 100, where 100 corresponds to maximum air quantity.
The adjustment is shown in the display.
The firing quantity and the air quantity must be adjusted according to each other.
Minimum output is 30% of full output. See also technical data.
Suggestions for adjustment - see, if necessary, section 1.10 - recommended adjustment
of the control.
(M) Firing at
intervals
This is set by means of the push button (M)
Set the number of minutes between each worm conveyor/auger delivery. This is only
active when the boiler temperature is rising. Set between 1 and 60 min so that the
fire can just be kept alight without firing so much that the temperature rises - this is
experience value.
Suggestions for adjustment - see, if necessary, section 1.10 - recommended adjustment
of the control.
(G) Manual worm conveyor - forward
This takes place by pressing on the symbol for the fuel worm conveyor/auger with the
arrow key to the right. As long as the key is activated, the worm conveyor/auger will run
inwards. However, this will not take place when the hopper is open.
(H) Manual worm conveyor/auger- backward
This takes place by pressing on the symbol for the worm conveyor/auger with the
arrow key to the left. As long as this key is activated, the worm conveyor/auger will
run outwards. However, not when the hopper door is open. Furthermore, the worm
conveyor/ auger can only run for 3 seconds if the key is depressed for a longer time.