inStructionS Pertaining to the inStaller
22. positioning of the ignition and flame sensing electrode
Figure 15
9912070100
The boiler has two connection points specifically designed to allow technicians to measure the combustion efficiency after
installation and ensure that the combustion products do not constitute a health risk.
One connection point is connected to the flue gas discharge circuit, and allows monitoring of the quality of the combustion
products and the combustion efficiency.
The other is connected to the combustion air intake circuit, allowing checking of any recycling of the combustion products
in case of coaxial pipelines.
The following parameters can be measured at the connection point on the flue gas circuit:
• temperature of the combustion products;
• oxygen (O
2
) or carbon dioxide (CO
2
) concentration;
• carbon monoxide (CO) concentration.
The combustion air temperature must be measured at the connection point on the air intake circuit, inserting the measurement
probe to a depth of about 3 cm.
For natural draught boiler models, a hole must be made in the flue gas discharge pipe at a distance from the boiler equal
to twice the inside diameter of the pipe itself.
The following parameters can be measured through this hole:
• temperature of the combustion products;
• oxygen (O
2
) or carbon dioxide (CO
2
) concentration;
• carbon monoxide (CO) concentration.
The combustion air temperature must be measured close to the point where the air enters the boiler.
The hole, which must be made by the person in charge of operating the system when it is commissioned, must be sealed
in a way which ensures that the combustion product discharge pipe is airtight during normal operation.
23. check of combustion parameters
This is a high static head pump fit for installation on any type of single or double-pipe heating systems. The air vent valve
incorporated in the pump allows quick venting of the heating system.
Graph 1
24. output / pump head performances
water flow rate
l/h
pu
M
p hea
D
m
h
2
o
0604_2302
Graph 2
water flow rate
l/h
pu
M
p hea
D
m
h
2
o
310 Fi
0604_2303
250 Fi
Summary of Contents for Luna 3 Comfort
Page 109: ...109 926 427 1 RU...
Page 113: ...113 926 427 1 RU 3 BAXI 3 2 3 3 1 0609_1901 0609_1902...
Page 114: ...114 926 427 1 RU 4 2 3 1 0605_1802 2 3 2 3 6 OFF 3 3...
Page 115: ...115 926 427 1 RU 3 4 1 3 1 1 1 HW SP 3 4 1 IP PROGR 1 Day 1 7 IP 3 5 prog 3 6 1 4 4 3 6...
Page 120: ...120 926 427 1 RU OFF 3 2 8 6 ERROR 0606_2207 9 7 15 20 5 30 8...
Page 136: ...136 926 427 1 RU 250 Fi 310 Fi 03 9 9 3 9 0 5 3 F17 20 30 5 30 25 9 24 10 24 3 NTC 21...
Page 137: ...137 926 427 1 RU 22 15 9912070100 2 2 3 2 2 23 1 24 2 310 Fi 250 Fi 0603_0303 0603_0304...
Page 141: ...141 926 427 1 RU 30...
Page 143: ...143 926 427 1 RU 32 0711_2806 CG_1980 NTC NTC N R G V B V 25...
Page 257: ...257 926 427 1 GR 3 2 Economy Comfort 0608_3101 3 Comfort 1 0609_1901 0807_1702 CG_2079 1 1 4...
Page 258: ...258 926 427 1 GR 3 2 3 1 0605_1802 2 4 2 COMFORT 3 6 Off 3 3...
Page 265: ...265 926 427 1 GR ERROR E 0606_2207 OFF 3 2 8 6 7 LPG 30 C 5 C 8 9 3 0901_0802 CG_1791...
Page 285: ...285 926 427 1 GR 30...
Page 287: ...287 926 427 1 GR 32 ntc ntc C M N R G V B V 25 0711_2806 CG_1980...