inStructionS Pertaining to the inStaller
B) change the modulator voltage
• setting
F02
parameter according to the gas used as described in section 20.
c) pressure adjusting device setting
• connect the positive pressure test point of a differential (possibly water-operated) manometer to the gas valve pressure
test point (
pb
) (Figure 13); connect, for sealed chamber models only, the negative pressure test point of the manometer
to a
“t”
fitting in order to join the boiler adjusting outlet, the gas valve adjusting outlet (
pc
) and the manometer. (The
same measurement can be carried out by connecting the manometer to the pressure test point (
pb
) after removing the
sealed chamber front panel);
If you measure the pressure of burners in a different way you may obtain an altered result in that the low pressure created
in the sealed chamber by the fan would not be taken into account.
c1) adjustment to nominal heat output
• open the gas tap;
• press
button (figure 1) and set the boiler in winter mode;
• open a hot water tap to reach a minimum
10 l/min
flow rate or ensure that maximum heating requirements are set;
• remove the modulator cover;
• adjust the tube brass screw (
a
) figure 14 to obtain the pressure settings shown in table 1;
• check that boiler feeding dynamic pressure, as measured at the inlet gas valve pressure test point (
pa
) (figure 13) is
correct (
37 mbar
for propane gas
G.31
,
20 mbar
for natural gas
G20
);
c2) adjustment to reduced heat output
• disconnect the modulator feeding cable and unscrew the (
b
) figure 14 screw to reach the pressure setting corresponding
to reduced heat output (see table 1);
• connect the cable again;
• fit the modulator cover and seal.
c3) Final checks
• apply the additional dataplate, specifying the type of gas and settings applied.
Figure 13
sit gas valve mod. siGMa 845
honeywell gas valve mod. vK 4105 M
0904_0701
table of burner pressures
250 Fi
310 Fi
Gas used
G20
G31
G20
G31
injector diameter (mm)
1,18
0,74
1,28
0,77
Burner pressure (mbar*)
1,9
4,9
1,8
4,9
table 1
reDuceD heat output
Burner pressure (mbar*)
11,3
29,4
13,0
35,5
nominal heat outPut
no. of injectors
15
* 1 mbar = 10,197 mm H
2
O
250 Fi
310 Fi
Gas consumption at 15 °c - 1013 mbar
G20
G31
G20
G31
Nominal heat output
2,84 m
3
/h
2,09 kg/h
3,52 m
3
/h
2,59 kg/h
table 2
reduced heat output
1,12 m
3
/h
0,82 kg/h
1,26 m
3
/h
0,92 kg/h
p.c.i.
34,02 MJ/m
3
46,3 MJ/kg
34,02 MJ/m
3
46,3 MJ/kg
Summary of Contents for Luna 3 Comfort
Page 109: ...109 926 427 1 RU...
Page 113: ...113 926 427 1 RU 3 BAXI 3 2 3 3 1 0609_1901 0609_1902...
Page 114: ...114 926 427 1 RU 4 2 3 1 0605_1802 2 3 2 3 6 OFF 3 3...
Page 115: ...115 926 427 1 RU 3 4 1 3 1 1 1 HW SP 3 4 1 IP PROGR 1 Day 1 7 IP 3 5 prog 3 6 1 4 4 3 6...
Page 120: ...120 926 427 1 RU OFF 3 2 8 6 ERROR 0606_2207 9 7 15 20 5 30 8...
Page 136: ...136 926 427 1 RU 250 Fi 310 Fi 03 9 9 3 9 0 5 3 F17 20 30 5 30 25 9 24 10 24 3 NTC 21...
Page 137: ...137 926 427 1 RU 22 15 9912070100 2 2 3 2 2 23 1 24 2 310 Fi 250 Fi 0603_0303 0603_0304...
Page 141: ...141 926 427 1 RU 30...
Page 143: ...143 926 427 1 RU 32 0711_2806 CG_1980 NTC NTC N R G V B V 25...
Page 257: ...257 926 427 1 GR 3 2 Economy Comfort 0608_3101 3 Comfort 1 0609_1901 0807_1702 CG_2079 1 1 4...
Page 258: ...258 926 427 1 GR 3 2 3 1 0605_1802 2 4 2 COMFORT 3 6 Off 3 3...
Page 265: ...265 926 427 1 GR ERROR E 0606_2207 OFF 3 2 8 6 7 LPG 30 C 5 C 8 9 3 0901_0802 CG_1791...
Page 285: ...285 926 427 1 GR 30...
Page 287: ...287 926 427 1 GR 32 ntc ntc C M N R G V B V 25 0711_2806 CG_1980...