COMMISSIONING THE FIRE - Page 12
Turn the control knob slowly to position 4, looking for
complete cross-lighting of the burner.
Check the setting pressure at position 4. No adjustment to
the setting pressure is possible.
(See Technical Data).
Turn the control knob to the ‘OFF’ (
)position.
Isolate the electricity supply.
Disconnect the pressure gauge, taking care not to touch any
hot surfaces and replace the pressure test point sealing
screw, ensuring a gas-tight seal.
Refit the electrical cover and reconnect the electricity supply.
SPILLAGE DETECTION
Check that the fire is fitted correctly.
Ensure that all the doors and windows in the room are
closed.
IMPORTANT NOTE: If there is an extractor or ceiling fan
in the room or any adjoining room, the check for
spillage must be performed with the fan turned on and
any interconnecting doors open.
Light the fire, turn to the full rate and leave for 5 minutes.
The fire should be checked visually for clearance of
products. Fit a lighted smoked match in a suitable holder and
position it in the downdraught diverter at either side of the
fire. Ensure that the majority of the smoke is drawn into the
chimney.
If there is any doubt, repeat the test after a further 10
minutes.
If there is any indication of spillage then the chimney may be
faulty. The cause of the fault must be identified and
corrected before the installation can proceed.
IF THE FAULT CANNOT BE RECTIFIED, TURN OFF AND
DISCONNECT THE GAS SUPPLY TO THE FIRE. SEEK
EXPERT ADVICE.