Operating the system
KSG 200 A/KSG 200 TA
28 / 60
822-170-3
5.3.2
Infocodes and their meaning
Code
Text on the back of the
receiver
Description
101
Connect transmitter and receiver. Press the
Start
button to calibrate.
122
Lay the receiver in the transmitter
bracket.
For the calibration, place the receiver in the transmitter
holder.
131
No signal.
This is not the searched cable.
Place the flexcoupler around another cable.
The loop resistance is too high.
132
Incorrect current polarity.
This is not the searched cable.
Flexcoupler is attached incorrectly.
Check the direction of the arrow on the flexcoupler. The
arrow must point in the direction of the cable end.
133
Loss of signal.
The signal decreases.
Possible causes: cable faults due to earth contact, T-branch or
earthed joints
138
Signal is too weak.
The amplitude fluctuations of the last three measurements were
too high. Therefore, no polarity and signal amplitude are
displayed.
139
No evaluation of signal amplitude
due to interferences.
The signal amplitude is not displayed, as it fluctuates greatly due
to interferences.
The pulse and its direction are identified.
180 –
184
No communication between
transmitter and receiver.
Receiver is not placed correctly in the transmitter holder.
Contacts on transmitter and/or receiver are dirty.
Clean the contacts.
190
Warning
: External voltage at
output.
KSG 200 (A): Risk of electric
shock!
Disconnect connection
cable from test object.
KSG 200 A: Disconnect the connection cable from the cable
that is to be identified. The connected cable is live.
You may carry out cable identification on live cables only with
KSG 200 TA.
KSG 200 T (A):
Note the
measurement category (CAT).
KSG 200 TA: Observe the safety instructions while carrying
out tasks on live cables.
193
Flexcoupler is defective.
During calibration and before each reading, the flexcoupler is
examined for any faults.
Contact BAUR After Sales Service and note down the
displayed infocode as well as the procedure that caused the
error.
194
Noise signal is too strong.
No measurement is possible. Due to high frequency noise
signals, the current pulse cannot be clearly detected.
195
Current is too high (I > 180 A).
Current pulse is greater than 180 A.