KSG 200 A/KSG 200 TA
Completing the cable identification
822-170-3
47 / 60
10.1 Safety instructions
Cable identification on de-energised cables
DANGER
Dangerous voltage in test object.
Danger to life or risk of injury due to electric shock.
Before touching the test object, discharge, earth and short it: at the
connection point and at the far end.
You may touch the parts that were under voltage only if they are
visibly earthed and short-circuited.
Cable identification on live cables
DANGER
Danger due to electric voltage, flashovers at the connection point,
or arcing fault on removing the connection
Danger to life or risk of injury due to electric shock, flashes.
Comply with EN 50110 or the applicable standards in your country
as well as the relevant national and local accident prevention
regulations for carrying out tasks in the vicinity of live parts.
Use suitable personal protective equipment to protect against arcing
faults and electric shocks.
Ensure that adjacent live parts are secured against accidental
contact and flashovers with suitable covers (insulation mats,
insulating safety plates).
Maintain safety distances. Safety distances depend on the voltage
level, plant model, personnel qualification and available space
(EN 50110).
10
C
OMPLETING THE C ABLE IDENTIFIC ATION