Installation
48
Mono Power Unit BUM 62, 63, 64
5.94005.12
Baumüller Nürnberg GmbH
y
X68 safety relay, 4-pin block connector (option)
It is possible to make the drive torque-free with the safety relay by switching off the +24 V on terminal
no. 3 and 4 (refer to “Safety relay” on page 33).
y
Terminal fan
Only BUM 64:
3-pin plug
(Part no. 19006141) supplied with the unit
Crimp contacts
(Part no. 19006141) supplied with the unit
Connection:
3 x 400 V / 0.23 A/0.27 A / 50/60 Hz, a pre-transformer must be used for other voltages
y
X60 64-pin plug
In order to connect the controller cassette to the motor-end converter, internal connection plug X 60 in
the cassette recess must be used.
For information on the controller cassette external connections, see the controller description.
Terminal-No.
Assignment
1, 2
Message contact 1 and 2,
Relay output 24 V, 0,5 A
3
Relay ON + 24 V
4
Relay ON ground
NOTE
The terminals 3 and 4 must be connected with +24 V
DC
while operation of the motor.
Safety relay OFF is stored as message and must be reset by a controller reset.
Summary of Contents for BUM 62
Page 1: ...E 5 94005 12 Manual Mono Power Unit BUM 62 63 64 ...
Page 8: ...Safety Notes 8 Mono Power Unit BUM 62 63 64 5 94005 12 Baumüller Nürnberg GmbH ...
Page 16: ...Transportation Unpacking 16 Mono Power Unit BUM 62 63 64 5 94005 12 Baumüller Nürnberg GmbH ...
Page 28: ...Installation 28 Mono Power Unit BUM 62 63 64 5 94005 12 Baumüller Nürnberg GmbH ...
Page 62: ...Commissioning 62 Mono Power Unit BUM 62 63 64 5 94005 12 Baumüller Nürnberg GmbH ...
Page 66: ...Maintenance 66 Mono Power Unit BUM 62 63 64 5 94005 12 Baumüller Nürnberg GmbH ...
Page 73: ......