Commissioning/Operation
Instruction handbook
b maXX
(BM4-F-)DIO/FIO-XX (Digital IO module)
Document No. 5.01046.06
49
8
8.2.2
Testing of the Digital IO module
Once the plug-in module has been recognized properly, then it can be checked whether
the input and outputs are working correctly using ProDrive.
Pre-conditions
Basic unit
b maXX
4000
has been commissioned,
BM4-F-DIO/FIO-XX
has been plugged in or
DIO/FIO-XX
is available (ES controller).
Digital connections are available/connected and ready for use (pin assignment see
V24 V
DC
(switchable) available on input 2.
h
ProDrive navigation „Diagnosis“, submenu „Service“.
h
In menu „Service“ is displayed wether the
Digital IO module
was recognized properly.
e.g. in line for
slot D
.
Testing the inputs 1
ProDrive navigation „IO digital inputs“.
2
Select in ProDrive „Digital input link 2“.
Figure 15:
Menu „Digital input link 2“
3
In this window, select the input point by the side of the selection „Input D.2“, when the
plug-in module is plugged in the slot D
4
Observe the replica of the LED and the text lying by its side „Input D.2 is low“.
5
In the window „Digital input link 2“, click on “...“ symbol by the side of „target parameter
number“.
A new window „IOs target parameter DI“.
6
From the list for selection of parameters, select „1000 = stipulated operating mode and
confirm with Ok.
The window gets closed again and the field under „target parameter number“ in the win-
dow „Digital input link 2 „ contains now the value „1000“.
7
In the window „Digital input link 2“, you click the “...“ symbol by „bit selection“, in the
window which appears now you enter with the value „&hFFFF“ and Ok.
The window closes again and the field under „bit selection“ in the window „Digital input
link 2“ now contains the value „FFFF“.