19
Instruction handbook
b maXX
(BM4-F-)AIO-XX (Analog IO module)
Document No.: 5.01045.08
3
T
ECHNICAL
D
ATA
3.1
Electrical data
1)
The analog outputs can be changed from „fast output“ to „slow output“ and vice versa by the operation soft-
ware.
(BM4-F-)AIO-
01
02
03
04
Number of inputs
2
Number of IO-input links
2
Resolution
10 bit / 12 bit
16 bit
12 bit
16 bit
Design
differential input circuit
Input resistance
ca. 50 k
Ω
ca. 100
Ω
Max. input current
200 µA
20 mA
Min. input current
-
4 mA
Sample rate inputs, one input used
125 µs
Sample rate inputs, both inputs used
250 µs
Max. analog input voltage
- 10 V to + 10 V
2 V
Number of outputs
2
1)
Number of IO-output links
2
Max. output current
1 mA
Resolution
8 bit
16 bit
12 bit
16 bit
Update-rate fast outputs
125 µs
Update-rate slow outputs
8 ms
Short-circuit protection output
limited short-circuit protection (max. 10 s)
Analog output voltage
- 10 V to + 10 V