Procedure of the commissioning
Instruction handbook
b maXX
(BM4-F-)AIO-XX (Analog IO module)
Document No.: 5.01045.08
Baumüller Nürnberg GmbH
52
8.2
3
By clicking on the
g
-symbol, select the entry „Input E.1“ („E“
⇒
module in position E,
„1“
⇒
input 1) from the drop-down list.
Figure 18:
Input selection AIO-04
4
Enter in menu „Analog input link 1“ :
m
Target parameter number
: „1171“, (ramp function generator input)
m
Smoothing time
: „10 ms“,
m
Scaling factor
: „1“,
m
Offset
: „0“,
m
Threshold
: „0“,
A scale is displayed and shows the applied current (set by the current calibrator), e. g.
+12 mA.
5
Check the display in „Analog input link 1“.
The RPM of the motor can be regulated now by the current calibrator.
6
Repeat the above steps for the input 2.
NOTE!
If for example, the scale shows 0 mA, even though there is a current applied on input
1 (see pin assignment
on page 39), then the input is defec-
tive. When changing the applied current, the relevant value of the current must be dis-
played on the scale.