23
VOL CALI
DATALOG
INFO
SETTING
MEASURE
CONTROL
HOME
20KVA
StanbyMode
19:52:36
2018-11-07
SYS PARAMETER
INSTALL INFO
VOL CALI
CURR CALI
231.3V
229.5V
Bus VOL
INITIAL
P
7.9V
6.2V
0.0%
N
BATT VOL
P
N
0.0%
0.0%
0.0%
VOL CALI Page1
Bus VOL: BUS voltage calibration. Increment of each click is 0.1% no matter it’s pressing up or down key
. Press “up” key to increase 0.1% and press “down” key to decrease 0.1%. Press “OK” key to confirm
the modification.
BATT VOL: Battery voltage calibration. Increment of each click is 0.1% no matter it’s pressing up or down
key
. Press “up” key to increase 0.1% and press “down” key to decrease 0.1%. Press “OK” key to
confirm the modification.
DATALOG
INFO
SETTING
MEASURE
CONTROL
HOME
20KVA
StanbyMode
19:52:36
2018-11-07
SYS PARAMETER
INSTALL INFO
VOL CALI
CURR CALI
120.0V
120.0V
Line VOL
INITIAL
R
120.0V
120.0V
0.0%
S
Output VOL
R
S
0.0%
0.0%
0.0%
T
T
0.0%
0.0%
120.0V
120.0V
VOL CALI Page2
Line VOL: Line voltage calibration. Increment of each click is 0.1% no matter it’s pressing up or down key
. Press “up” key to increase 0.1% and press “down” key to decrease 0.1%. Press “OK” key to confirm
the modification.
Output VOL: Output voltage calibration. Increment of each click is 0.1% no matter it’s pressing up or
down key
. Press “up” key to increase 0.1% and press “down” key to decrease 0.1%. Press “OK” key to
confirm the modification.