31
DATALOG
INFO
SETTING
MEASURE
CONTROL
HOME
20KVA
Bypass Mode
19:52:36
2018-11-07
BASIC
RATED
PARAMETER
Line VOL Range
Line FRE Range
Bypass VOL Range
Bypass FRE Range
56.0Hz
80V
96V
ECO VOL Range
ECO FRE Range
56.0Hz
115V
58.0Hz
156V
64.0Hz
146V
64.0Hz
125V
62.0Hz
Parameter Information Page 1
Parameter Information
Line Voltage Range: The acceptable line input voltage range.
Line FRE Range: The acceptable line input frequency range.
Bypass Voltage Range: The acceptable input voltage range for bypass mode.
Bypass FRE Range: The acceptable input frequency range for bypass mode.
ECO Voltage Range: The acceptable input voltage range for ECO mode.
ECO FRE Range: The acceptable input frequency range for ECO mode.
DATALOG
INFO
SETTING
MEASURE
CONTROL
HOME
20KVA
Bypass Mode
19:52:36
2018-11-07
BASIC
RATED
PARAMETER
BATTMode Work Time
BATT Warning VOL
HIGH
Shutdown VOL
990Min
Shutdown Delay
Restore Delay
10.7V
0min
0min
14.4V
11.5V
10
LOW
BATT Number
Parameter Information Page 2
BATT Mode Work Time: The maximum discharge time in battery mode.
BATT Warning Voltage:
HIGH: High battery warning voltage.
LOW: Low battery warning voltage.
Shutdown Voltage: If battery voltage is lower this point, UPS will automatically shut down.
Shutdown Delay: UPS will shut down in setting minutes. The countdown will start after confirming the
pop-up screen.
Restore Delay: UPS will automatically restart in setting minutes after the UPS shuts down.
Battery Number: It shows battery number.
3-3-6. Data Log screen
Touch the icon
to enter date log page. Data log is used to record the warning and fault information of
the UPS. The record contains date & time, code, type and description. Touch the icon
or
to
page up or down if there are more than one page in the date log. Touch the icon
to return to main
screen. Press the icon
to go back to main menu. Please refer to Section 3-7 and 3-8 for warning and