29
Auto Restart:
Enable: After “Enable” is set, once UPS shutdown occurs due to low battery and then utility
restores, the UPS will return to line mode.
Disable: After “Disable” is set, once UPS shutdown occurs and the utility restores, the UPS will
not automatically turn on.
Shutdown Delay Min: UPS will shut down in setting minutes. The countdown will start after confirming
the pop-up screen.
Restore Delay Min: UPS will automatically restart in setting minutes after the UPS shuts down.
New Password: Set up User new password to enter ADVANCE User?? menu page.
DefaultUserPassword:
YES: After “YES” is set, User password will restore default setting value.
NO: After “NO” is set, the UPS will cancel this operation.
UPS SELFTEST
unknown
R-Phase
PFC Test Step:
0
0
INV Test Step:
S-Phase
T-Phase
unknown
unknown
unknown
unknown
unknown
R-Phase
S-Phase
T-Phase
This function is only effective when UPS type setting is “HV”. Therefore, please disconnect all loads and
utility first before executing this function. Then, please change UPS type to “HV”. For the detailed operation,
please check “System Parameter” menu under Advance
Maintainer directory.
After changing UPS type to “HV”, you have to restart the UPS. After the UPS is restarted, please enter
Advance screen and enter Maintainer password. It will show “UPS SELFTEST” selection in the screen. In the
screen, all tested items are shown “unknown”. Simply click “UPS SELFTEST” button, the UPS will start
self-test. If the UPS is normal, it will show “Normal” in all columns. Otherwise, “Unknown” will be displayed
in the columns.