27
ELECTRICAL
DATALOG
INFO
SETTING
MEASURE
CONTROL
HOME
20KVA
Bypass Mode
19:52:36
2018-11-07
ELECTRONIC
BATTERY
MISCELLANEOUS
OUTPUT VOL
OUTPUT FRE
CVCF Mode
Bypass Forbid
120V
60Hz
Disable
Disable
UPS SELFTEST
Electrical Setting Page 1
Output Voltage: Select the output rated voltage.
There are two options, 120V and 127V. 120Vac is default setting.
Output Rated FRE: Select output rated frequency.
50Hz: The output frequency is setting for 50Hz.
60Hz: The output frequency is setting for 60Hz.
CVCF Mode (constant voltage and constant frequency function)
Enable: CVCF function is enabled. The output frequency will be fixed at 50Hz or 60Hz according to
setting of “Output Freq.”. The input frequency could be from 40Hz to 70Hz.
Disable: CVCF function is disabled. The output frequency will synchronize with the bypass
frequency within 45~55 Hz for 50Hz system or within 55~65 Hz for 60Hz system. Disable is the
default setting.
Bypass Forbid:
Enable: Bypass Forbid is enabled. It’s not allowed for running in Bypass mode under any
situations.
Disable: Bypass Forbid is disabled. UPS will run in Bypass mode. It is the default setting.
DATALOG
INFO
SETTING
MEASURE
CONTROL
HOME
20KVA
Bypass Mode
19:52:36
2018-11-07
ELECTRONIC
BATTERY
MISCELLANEOUS
Bypass UPS Off
Bypass VOL Range
Bypass FRE Range
ECO Mode
96V
Enable
Disable
ECO VOL Range
ECO FRE Range
146V
64.0Hz
56.0Hz
115V
125V
58Hz
62Hz
UPS SELFTEST
Electrical Setting Page 2
Bypass at UPS off: Select the bypass status when manually turning off the UPS. This setting is only
available when “Bypass forbid” is set to “Disable”.
Enable: Bypass enabled. When selected, bypass mode is activated.
Disable: Bypass disabled. When selected, no output through bypass when manually turning off
the UPS.
Bypass Voltage Range: Set the bypass voltage range.
L: Low voltage point for bypass. The setting range is 96V ~ 110V. 96V is default setting.