22
Mode Name: Set the UPS model name.
Serial Number: Set the serial number.
Manufacturer: Set the UPS manufacturer.
Charge MaxCURR: The maximum of battery charging current. This parameter setting is related to
“Charger Number” setting (check next page for the details).
One piece of charger: There are four options, 1A, 2A, 3A, 4A. 4A is default setting.
Two pieces of charger: There are two options, 4A, 8A. 8A is default setting.
Three pieces of charger: There are three options, 4A, 8A, 12A. 12A is default setting.
BATT Number: The total number of installed battery. (It should be restart UPS after setting.) The setting
range is 8 ~ 10. 10 is default setting.
Charge VOL: The setting point of battery float voltage. 13.6V is default setting.
DATALOG
INFO
SETTING
MEASURE
CONTROL
HOME
20KVA
StanbyMode
19:52:36
2018-11-07
SYS PARAMETER
INSTALL INFO
VOL CALI
CURR CALI
LV
Charger Number
INITIAL
UPS Type
3PCS
SYS PARAMETER Page 2
Charger Number: The number of charging boards installed on the UPS.
NOTE: It’s required to restart the UPS after setting.
One piece of charger: When selected, there are four options available for “Charger MaxCURR”.
Two pieces of charger: When selected, there are two options available for “Charger MaxCURR”.
Three pieces of charger: When selected, there are three options available for “Charger
MaxCURR”.
UPS Type: There are two options, HV and LV. This change is only allowed for qualified technician.
NOTE: It’s required to restart the UPS after setting.
INSTALL INFO
DATALOG
INFO
SETTING
MEASURE
CONTROL
HOME
20KVA
StanbyMode
19:52:36
2018-11-07
SYS PARAMETER
INSTALL INFO
VOL CALI
CURR CALI
2018
1
SYS Install Date
INITIAL
BAT Install Date
2018
1
1
1
INSTALL INFO Page
SYS Install Date: Set the date of UPS installation.
BAT Install Date: Set the date of Battery installation.