BE1-51C General Information
1-3
neutral flag
xxxx xxxx
|||| ||||--neutral function active
|||| |||----50g function active
|||| ||-----51g function active
|||| |-------affected output (0 = normal = TIMED and INST1, 1 = INST2)
Following are examples of the internal flags. When the setting is handled from the front panel, these flags
are not available to the user. When the setting is from the computer, these flags are needed.
Partial list of examples (function 07 is identical to units version 1.5 and previous).
FLAG
DESCRIPTION
0000 xxx0
Neutral function selectivity completely disabled (same functionality as 07h)
0000 0011=03h
Neutral function enabled for 50 element
Neutral function disabled for 51 element
Functions incorporated into existing output relays (51, INST1)
0000 0101=05h
Neutral function enabled for 51 element
Neutral function disabled for 50 element
Functions incorporated into existing output relays (51, INST1)
0000 0111=07h
50g and 51g both enabled
Neutral functions incorporated with phase functions (51, INST1)
This is how BE1-51C/SCOR version 1.5 and previous functioned.
0000 1011=0bh
Neutral function disabled for 51 element
Neutral function enabled for 50 element
Functions removed from existing output relays and grouped into INST2
output relay
0000 1101=0dh
Neutral function enabled for 51 element
Neutral function disabled for 50 element
Functions removed from existing output relays and grouped into INST2
output relay
0000 1111=0fh
Neutral function enabled for 51 element
Neutral function enabled for 50 element
Functions removed from existing output relays and grouped into INST2
output relay
BREAKER FAILURE
This standard feature invokes a breaker failure function within the relay. If enabled (reg 68=01) the function
occurs as follows.
The breaker failure function involves a 1 second timer. When a trip occurs, the timer starts. At timeout, two
checks are made: one, that the breaker properly changed state, and two, that the current is below approx
10% of the tap value. If the results of either check is not correct, then a breaker failure has occurred.
Summary of Contents for BE1-51C
Page 12: ...BE1 51C General Information 1 6 Figure 1 1 Style Number Identification Chart...
Page 21: ...BE1 51C Controls and Indicators 2 2 Figure 2 1 Location of Controls and Indicators...
Page 25: ...BE1 51C Functional Description 3 2 Figure 3 1 Functional Block Diagram...
Page 49: ...BE1 51C Operation By Computer 5 14 Figure 5 1 RS 232 Port Connector Wiring...
Page 50: ...BE1 51C Operation By Computer 5 15 Figure 5 2 RS 485 Port Connector Wiring...
Page 58: ...BE1 51C Installation and Testing 6 8 Figure 6 1 Outline Dimensions...
Page 62: ...BE1 51C Installation and Testing 6 12 Figure 6 8 Relay Connections...