BE1-51C General Information
1-7
I
K
T
BE1-51C SPECIFICATIONS
The BE1-51C relay is available in single-phase, three-phase, two-phase-with-neutral, and three-phase-with-
neutral configurations, and with the following features and capabilities.
Current Sensing Inputs
The unit is designed to operate from the secondary of a standard current
transformer rated at 5 A. The maximum continuous current rating for each
input is five times tap or 20 A, whichever is less.
The one-second current rating for each input is 50 times tap or 500 A,
whichever is less. Ratings at less than one second are calculated as:
where
K = (500 A or 50 times TAP)
2
T = Time that current flows (in seconds)
Current Sensing Burden
Less than 0.1 ohm.
Frequency (nominal)
60 Hz.
Time Overcurrent
Pickup Ranges
Two ranges are available: HIGH (2-11 A), and LOW (0.5-5 A). Range is
independently specified for phase and neutral by the second digit of the
Style Number. The TAP range plate(s) on the front panel indicate which
range (HIGH or LOW) is specified.
Pickup Adjustment
Incrementally adjustable over the selected range by a front-panel (TAP)
selector switch (coarse), and by numerical data entered into the Tap Cal
register (fine).
Pickup Setting Accuracy
The accuracy of the pickup setting is ±2% of the programmed setting over
the full specified range of the relay at 60 Hz.
Pickup Repeatability
Within 2%.
Dropout Ratio
Better than 80% of the established pickup level within 50 milliseconds.
Instantaneous Overcurrent
Pickup Range
0.5 to 20 times the value of the time overcurrent pickup setting.
Pickup Setting Accuracy
The accuracy of the instantaneous pickup setting is ±2% of the
programmed setting over the full specified range of the relay at 60 Hz.
Pickup Repeatability
Within 2%.
Dropout Ratio
Better than 80% of the established pickup level within 50 milliseconds.
Summary of Contents for BE1-51C
Page 12: ...BE1 51C General Information 1 6 Figure 1 1 Style Number Identification Chart...
Page 21: ...BE1 51C Controls and Indicators 2 2 Figure 2 1 Location of Controls and Indicators...
Page 25: ...BE1 51C Functional Description 3 2 Figure 3 1 Functional Block Diagram...
Page 49: ...BE1 51C Operation By Computer 5 14 Figure 5 1 RS 232 Port Connector Wiring...
Page 50: ...BE1 51C Operation By Computer 5 15 Figure 5 2 RS 485 Port Connector Wiring...
Page 58: ...BE1 51C Installation and Testing 6 8 Figure 6 1 Outline Dimensions...
Page 62: ...BE1 51C Installation and Testing 6 12 Figure 6 8 Relay Connections...