Table 1-2. Timing, Curve B4, BE1-51/27R At 25% Voltage (20 to 99 Time Dial Settings) - Continued
Multiple of
Setting
Multiple of
Pickup
Time Dial Setting (Seconds)
20
30
40
50
60
80
99
1-4
BE1-51/27R - General Information
0.63
2.50
2.766 4.003 5.218 6.454 7.682 10.146 12.453
0.68
2.70
2.569 3.720 4.848 5.986 7.130 9.381 11.557
0.75
3.00
2.322 3.358 4.372 5.409 6.434 8.489 10.454
0.88
3.50
2.026 2.931 3.829 4.726 5.627 7.406 9.120
1.00
4.00
1.833 2.647 3.450 4.258 5.076 6.688 8.214
1.13
4.50
1.691 2.438 3.188 3.932 4.673 6.166 7.597
1.25
5.00
1.464 2.117 2.749 3.380 4.022 5.303 6.513
1.50
6.00
1.424 2.060 2.688 3.314 3.949 5.200 6.396
1.75
7.00
1.318 1.897 2.479 3.060 3.644 4.802 5.899
2.00
8.00
1.234 1.792 2.329 2.884 3.430 4.518 5.561
2.25
9.00
1.184 1.704 2.229 2.748 3.273 4.298 5.290
2.50
10.00
1.120 1.604 2.093 2.589 3.070 4.053 4.977
3.00
12.00
1.073 1.551 2.018 2.498 2.971 3.917 4.817
3.50
14.00
1.028 1.481 1.928 2.390 2.841 3.741 4.603
4.00
16.00
0.989 1.430 1.866 2.304 2.741 3.610 4.443
4.50
18.00
0.958 1.392 1.818 2.243 2.667 3.514 4.328
5.00
20.00
0.944 1.372 1.786 2.200 2.619 3.454 4.252
STANDARD FEATURES
Time Overcurrent
Time overcurrent elements pick up over a range of 0.1 to 0.8 amperes, 0.3 to 2.4 amperes, 0.5 to 4.0
amperes, 1.5 to 12.0 amperes, 0.1 to 2.4 amperes, or 0.5 to 12.0 amperes and provide an adjustable time
delay that is proportional to the overcurrent. Time delay is initiated when the sensed current exceeds the
pickup point. When the current drops below the pickup point, the timing circuit is reset immediately. At
reset, the output contacts, if operated, are restored to normal.
Adjustment of the overcurrent pickup point is provided by controls on the relay front panel. Time delay is a
function of the characteristic curve that has been selected. Time delay is adjustable from 00 to 99 on the
front panel Time DIAL thumbwheel switch. Curve type is either selected as an option or, in some models,
selected by a switch that is located behind the front panel.
Sixty-nine characteristic curves and three timing options are available. They are:
Characteristic curves:
Seven inverse time
Nine I
2
T
Seven inverse time with extended timing range