BE1-51/27R - Tests And Adjustments
5-5
NOTE
During this test, disregard any indication on the test setup timer.
Figure 5-6. Test Setup for Sensing Input Type Y or Z (Two-Phase with Neutral Sensing)
Step 6.
Ensure that the relay front panel TARGETS, if present, are reset.
Step 7.
Apply 100% of nominal voltage based on the sensing input type for your relay.
Time Overcurrent Pickup Test
This test will check the minimum and maximum overcurrent pickup points of the time overcurrent element.
Step 1.
Perform the Preliminary Instructions.
Step 2.
Set the front panel TAP selector to A.
Step 3.
Adjust the test set, for an overcurrent threshold having one of the following values:
a) 0.5 A for relays with Sensing Input Range 1, 2, or 4.
b) 1.5 A for relays with Sensing Input Range 3 or 5.
Step 4.
Slowly adjust the front panel TAP CAL control CCW until the front panel TIMING Indicator
illuminates.
RESULT: For the phase minimum overcurrent pickup point of 0.5 A (Step 3a., above) or 1.5 A
(Step 3b., above) the front panel TAP CAL control should be near its maximum CCW limit.
Step 5.
Adjust the front panel TAP CAL control fully CW to allow measurement of the actual overcurrent
pickup point at the A setting of the front panel TAP selector. Note that the front panel TIMING
Indicator will extinguish. Do not disturb this setting.