1-12
BE1-51/27R - General Information
UL Recognized
UL Recognized per Standard 508, UL File No. E97033. Note: Relay is
not UL Recognized for output contact voltages greater than 250 volts
and input power supply voltages greater than 150 volts.
Operating Temperature
-40
C (-40
F) to +70
C (+158
F).
Storage Temperature
-65
C (-85
F) to +100
C (+212
F).
Shock
In standard tests, the relay has withstood 15 g in each of three mutually
perpendicular planes without structural damage or degradation of per-
formance.
Vibration:
In standard tests, the relay has withstood 2 g in each of three mutually
perpendicular planes, swept over the range of 10 to 500 Hz for a total of
six sweeps, 15 minutes each sweep, without structural damage or deg-
radation of performance.
Weight
Single-Phase: 13.0 lbs. (5.9 kg)
Three-Phase: 14.0 lbs. (6.4 kg)
Three-Phase-and-Neutral: 14.4 lbs. (7.2 kg)
Case Size
S1.
TIME OVERCURRENT CHARACTERISTIC CURVES
Graphs on the following pages illustrate sample characteristic curves for all of the time overcurrent
functions individually as options, or selected by switch (if the Z1, Z2, or Z3 timing option is specified). Z1
option can select any of the timing types designated as B1 through B8, and C1 through C8. Z2 option
can select any of the timing types designated as B1 through B8, and the British Standard timing types:
E2, E4, E5, E6, and E7. Z3 option can select the integrating algorithm for any of the timing types
designated as B1 through B8, and C1 through C8.
Note that there are two versions of each timing type: standard and extended timing. Both types are
located on the same page. The exception to this is the British Standard curves which do not have an
extended timing version. For any given relay, either the standard or the extended range version will
apply, never both.
A drawing number is provided with each characteristic curve chart. Use this number to order the full-size
(11" X 17") characteristic curve chart on transparent paper (vellum). Publication 9 1372 00 897 contains
36 full size characteristic curve charts (timing options Z1 and Z2). To order any of these characteristic
curve charts, contact
Customer Service Department of the Power Systems Group, Basler Electric.