BE1-32R, -32 O/U GENERAL INFORMATION
1-13
Figure 1-13. Underpower Instantaneous Response Time
Power Range (Pickup)
Adjustable over the ranges listed in Table 1-3.
Isolation
In accordance with IEC 255-5 and ANSI/IEEE C37.90, one minute dielectric
(high potential) tests as follows:
All circuits to ground:
2121 Vdc
Input to output circuits:
1500 Vac or 2121 Vdc
Radio Frequency
Maintains proper operation when tested for interference in accordance
Interference (RFI)
with IECC C37.90-1989, Trial-Use Standard Withstand Capability of Relay
systems to Radiated electromagnetic Interference from Transceivers.
UL Recognized
UL Recognized per Standard 508, UL File No. E97033. Note: Output contacts
are not UL Recognized for voltages greater than 250 volts.