5-8
BE1-32R, -32 O/U INSTALLATION
I
0.5 ×
W
V
NOTES:
1.
Type E sensing is calibrated in three-phase watts using single-phase sensing inputs. Using the test
setup shown, the relay may be calibrated in true three-phase power using one-half the pickup
current corresponding to the desired overpower or underpower pickup in watts. Adjust the relay
test set to produce this current value from the following equation.
Where:W
=
Desired pickup in watts
V
=
Applied voltage
I
=
Applied current
With a wattmeter:
W
2 × Wattmeter Reading
2.
Terminals 1 and 10 are the overpower trip output device connections for both BE1-32R and BE1-32
0/U. Terminals 2 and 10 are the underpower output connections for the BE1-32 0/U.
3.
Terminals 17 thru 20 are auxiliary relay output contacts. Determine the auxiliary output contact
configuration by referring to the relay style number.
Figure 5-5. Type E Sensing Test Setup Diagram