BE1-32R, -32 O/U GENERAL INFORMATION
1-11
Output Circuits
Output contacts are rated as follows:
Resistive:
120/240 Vac
Make 30 A for 0.2 seconds, carry 7 A continuously, and break 7 A.
250 Vdc
Make 30 A for 0.2 seconds, carry 7 A continuously, and break 0.3 A.
Inductive:
120/240 Vac,
Make and carry 30 A for 0.2 seconds, carry 7 A continuously, and break
125/250 Vdc
0.3 A. (L/R = 0.04).
Power Supply
Table 1-2. Power Supply Specifications
Type
Nominal
Input
Voltage
Input
Voltage
Range
Burden
at
Nominal
O (Mid Range)
48 Vdc
24 to 150 Vdc
5.0 W
P (Mid Range)
125 Vdc
120 Vac
24 to 150 Vdc
90 to 132 Vac
5.2 W
15.1 VA
†R (Low
Range)
24 Vdc
12 to 32 Vdc
5.1 W
T (High Range)
250 Vdc
240 Vac
62 to 280 Vdc
90 to 270 Vac
5.2 W
14.0 VA
NOTES: All references are at 50/60 Hz.
†
Type R Power Supply may require 14 Vdc to begin operation. Once oper-
ating, the voltage may be reduced to 12 Vdc.
Pickup Accuracy
Single Phase
PF = 1
±2 percent of front panel setting or 0.05 watts (whichever is greater).
.5<PF<1
±5 percent of front panel setting or 0.05 watts (whichever is greater).
Three Phase
PF =1
±2 percent of front panel setting or 0.15 watts (whichever is greater).
.
5<PF<1
±5 percent of front panel setting or 0.15 watts (whichever is greater).
Pickup Dropout Accuracy
95 percent of actual pickup.
Timing Adjustment Range
Instantaneous
Overpower
The overpower instantaneous response time is less than 80 ms, 60 Hz or less
than 100 ms, 50 Hz for real power magnitude of 2 times the setting and greater.
The response time is characterized by the graph in Figure 1-12.
Underpower
The underpower instantaneous response time is less than 50 ms, 60 Hz or less
than 65 ms, 50 Hz for real power magnitude of .8 times the setting and less.
The response time is characterized by the graph in Figure 1-13.
www
. ElectricalPartManuals