5-4
BE1-32R, -32 O/U INSTALLATION
W
V
A
× I
NOTES:
1.
Type A sensing is calibrated in single-phase watts. If a wattmeter is not available, use the following
equation to determine the pickup current corresponding to the desired overpower or underpower
pickup in watts. Adjust the relay test set to produce this current value.
Where:W
=
Desired pickup in watts (front panel setting)
V
=
Applied voltage
I
=
Applied current
With a wattmeter:
W
Wattmeter Reading
2.
Terminals 1 and 10 are the overpower trip output device connections for both BE1-32R and BE1-32
0/U. Terminals 2 and 10 are the underpower output connections for the BE1-32 0/U.
3.
Terminals 17 thru 20 are auxiliary relay output contacts. Determine the auxiliary output contact
configuration by referring to the relay style number.
Figure 5-1. Type A Sensing Test Setup Diagram