FWG09I Assembly instructions
18
Example periodic call, car 1, program 1, PIN *4711*
A periodic call takes place every 3 days. In there is no periodic call, the lift system must be shut down,
since the emergency call is presumably no longer working:
1.
Unit dials extension.
2.
Call is accepted, then an announcement from the unit is made: “
Object number <
Object>
”,
then the messages:
“
Periodic call car 1
”
“
Please enter PIN to clear the notifications
” – Indication of acknowledgement.
3.
Enter PIN: “
*4711*
”. Response from unit: “
Messages cleared
”
4.
Hang up
The periodic call must be documented with date and time.
The messages, their reports and recommended measures
Alarms
Emergency car n (All Programs)
An alarm was triggered in the car.
Recommendations for action: Receiving the alarm, establishing the voice communication, ending the
voice communication and if necessary freeing persons.
Misuse car n (All Programs)
The alarm button is pressed if the unit is set to “Misuse on” and voltage simultaneously applied at
the misuse input.
Recommendations for action: Establish voice communication and respond accordingly.
Emergency over car n (Programs 1, 2, 2A)
An active emergency call has been marked as finished on the emergency call device. It is to be
assumed that a technician is on site.
Recommendations for action: Not required as there is a technician on-site.
Periodic calls
Periodic calls are carried out every 72 hours to check whether accepting the emergency call is still
possible. For this reason, each periodic call is to be documented with the date and time, and the time
of the next expected periodic call is to be set to 72 hours later. If this does not happen or is delayed
without any discernible reason, the lift system must be shut down!
After a warm start and cold start, the time until the next periodic call is reset to 72 hours later;
therefore the time of the next expected periodic call must also be reset accordingly.
Periodic call car n (Programs 1, 2A)
This is the normal periodic call.
Recommendations for action: Document date and time, set the time of the next expected periodic
call to 72 hours from now. If this does not happen, the lift system must be shut down!