Operation and Installation Manual PBTC-300
21-54C3-7D0002/-
01/2022-EHT-441169
Notice:
Technical data subject to change without notice.
No claims for damage arising from alternations, errors or misprints shall be allowed.
Seite 4 / 49
2
Safety Instructions
2.1
Intended Use
The junction box with electronic thermostat module PBTC is intended for use as a temperature controller in electrical trace heating
systems.
The junction box with electronic thermostat module may only be installed in trace heating systems that have been designed by trained
and qualified personnel with specific expertise and experience in explosion protection and trace heating systems.
It can be operated only with
Resistance Temperature Device Pt100
Appropriately designed over-current protection device
The self-limiting BARTEC heating cables type PSB, MSB, HSB+ or HTSB
End cap mounted on the heating pipe end
Completely filled out acceptance test report
The junction box with electronic thermostat module may only be operated with one heating cable; the maximum permissible heating
cable length must be observed.
The approval and marking of the respective heating system, the data sheet of the heating cable type and the design guide must be
observed.
For use with electrical systems, the relevant installation and operating conditions (e.g. according to ATEX Directive 2014/34/EU, EN
60079-0, EN 60079-14, EN 60079 17, EN 60079 30 2 and any other relevant national standards) must be observed. Information on
the type plate, the EU type examination certificate must be observed. Technical data on the thermostat module and in the operating
instructions must be observed.
2.2
Approval and marking
Approvals and markings of the Junction Box with Electronic Thermostat Module PBTC:
Junction Box with Electronic Thermostat Module PBTC
IECEx IBE 12.0031 X
Ex eb mb [ib] [60079-30-1] IIC T4, T5 Gb
Ex tb [ib] [60079-30-1] IIIC T135°C, T95°C Db
IBExU 12 ATEX 1099 X
II 2G Ex eb mb [ib] [60079-30-1] IIC T4, T5 Gb
II 2D Ex tb [ib] [60079-30-1] IIIC T135°C, T95°C Db
For the trace heating system used with in the Junction Box with Electronic Thermostat Module is installed, the following approvals
and markings are applicable depending on the selected heating cable:
PSB-Heating system
IECEx KEM 09.0084X
Ex e IIC T5,T6 Gb
Ex tb IIIC T85°C T100°C Db
KEMA 08 ATEX 0111 X
II 2G Ex e IIC T5,T6 Gb
II 2D Ex tb IIIC T85°C T100°C Db
MSB-Heating system
IECEx KEM 09.0083X
Ex e IIC T4, T3 Gb
Ex tb IIIC T130°C, T200°C Db
KEMA 08 ATEX 0110 X
II 2G Ex e IIC T4, T3 Gb
II 2D Ex tb IIIC T130°C, T200°C Db
HSB+ -Heating system
IECEx CML 19.0008
Ex e IIC T3 Gb
Ex tb IIIC T200°C Db
CML 19 ATEX 3033
II 2G Ex e IIC T3 Gb
II 2D Ex tb IIIC T200°C Db