Operation and Installation Manual PBTC-300
21-54C3-7D0002/-
01/2022-EHT-441169
Notice:
Technical data subject to change without notice.
No claims for damage arising from alternations, errors or misprints shall be allowed.
Seite 21 / 49
9
Installation and Assembly
The required mounting material for mounting the PSB and MSB heating cable types is enclosed with the product. The CAK-SRB is
required for mounting the HSB+ and HTSB heating cable types. It may have to be ordered separately.
Required Tools / Equipment
The following tools and equipment are required for installa-
tion of the PBTC-300:
Wire cutters
Flat screwdriver 3.5mm
Phillips screwdriver
size 2
Flat screwdriver 2.5mm
Tape measure
Cutter knife
Needle-nose pliers (2x)
Adjustable wrench (2x)
Safety Instructions
WARNING
Fire and electric shock hazard due to electrical trace
heating system
Risk of injury due to electric voltage
When starting installation and maintenance work, dis-
connect all circuits from the power supply and check
that there are voltage-free!
Operate electrical trace heating systems with residual
current protection device!
Connect one heating cable per Junction Box only
Connect permitted heating cable types only
Observe maximum permissible heating circuit length
Observe Design Guide for trace heating systems
Observe the project planning documentation of the trace
heating system
Installing the Heating Cable
Install the heating cable in a straight line along the pipe if
possible
If possible, install the heating cable in the lower half of the
pipe, but not at the lowest point
If necessary, return the heating cable loop to the heating
cable at the greatest possible distance
Install the Resistance Temperature Device directly on the
pipe
Install the Resistance Temperature Device in the lower
area of the pipe cross section
Install the Resistance Temperature Device at the greatest
possible distance from the heating cable
Observe additionally required heating cable lengths (as-
sembly of connections, T-branches and end terminations,
each approx. 0.5 m)
Avoid damage to the heating cable and the Resistance
Temperature Device: no bending, pinching or pulling over
sharp edges
2 x
1
2
3
2 x
Summary of Contents for PBTC-300