Manual 2100-652A
Page
4 of 42
TABLE 1
Factory Built-In Electric Heat
(See Table 2 for available electric heat by unit model)
Nominal
KW
At 240V
At 208V
At 480V
At 460V
KW
1-Ph
Amps
3-Ph
Amps
BTUH
KW
1-Ph
Amps
3-Ph
Amps
BTUH
KW
3-Ph
Amps
BTUH
KW
3-Ph
Amps
BTUH
5.0
5.0
20.8
17,065
3.75
18.0
12,799
6.0
6.0
14.4
20,478
4.50
12.5
15,359
6.0
7.2
20,478
5.52
6.9
18,840
9.0
9.0
21.7
30,717
6.75
18.7
23,038
9.0
10.8
30,717
8.28
10.4
28,260
10.0
10.0
41.7
34,130
7.50
36.1
25,598
12.0
12.0
28.9
40,956
9.00
25.0
30,717
12.0
14.4
40,956 11.04
13.9
37,680
15.0
15.0
62.5
36.1
51,195 11.25
54.1
31.2
38,396
15.0
18.0
51,195 13.80
17.3
47,099
These electric heaters are available in 230/208V units only.
These electric heaters are available in 480V units only.
Q-TEC SERIES GENERAL INFORMATION
Q-TEC MODEL NOMENCLATURE
Q
36
H
3 – A
10
X
X
V
X
X
X
REVISION
VOLTS & PHASE |
A – 230/208/60/1
B – 230/208/60/3
C – 460/60/3
INTERNAL CONTROLS
X – Standard
• High Pressure Switch
• Low Pressure Switch
• Compressor Time Delay
E – Low Ambient Control
Q – Outdoor Thermostat
R – Low Ambient Control and
Outdoor Thermostat
CLIMATE CONTROL OPTIONS
X – None
D – Electronic/Prog/Man/Auto
H – Electronic/Prog/Man/Auto with CO
2
B – Electronic/Prog/Humidistat/BACNet
C – Electronic/Prog/Humidistat/BACNet/CO
2
MODEL
NUMBER
CAPACITY |
24 – 2 Ton
30 – 2½ Ton
36 – 3 Ton
43 – 3½ Ton
48 – 4 Ton
60 – 5 Ton
KW
0Z – 0KW
05 – 5KW
06 – 6KW
09 – 9KW
10 – 10KW
12 – 12KW
15 – 15KW
VENTILATION OPTIONS
X – Barometric Fresh Air Damper (Standard)
B – Blank-off Plate
V – Commercial Ventilator – Motorized w/Exhaust
Spring Return
P – Commercial Ventilator – Motorized w/Exhaust
Power Return
R – Energy Recovery Ventilator w/Exhaust
FILTER OPTIONS
X – 1" Fiberglass
(Standard)
F – 2" Fiberglass
P – 2" Pleated
COLOR OPTIONS
V – Platinum w/Slate
Front (Vinyl)
X – Beige paint
4 – Gray paint
HEAT
PUMP
COIL OPTIONS
X – Standard
1 – Phenolic coated
evaporator*
2 – Phenolic coated
condenser
3 – Phenolic coated
evaporator and
condenser
coil*
*and reheat if
applicable