Manual 2100-652A
Page
41 of 42
MODEL
RETURN
AIR
TEMP.
PRESSURE
AIR TEMPERATURE ENTERING OUTDOOR COIL
75°
80°
85°
90°
95°
100°
105°
110°
115°
120°
Q24H3
75 DB
62 WB
Low Side
High Side
118
326
119
340
121
358
122
377
125
399
128
422
132
449
135
477
138
508
140
525
80 DB
67 WB
Low Side
High Side
126
334
127
349
129
367
131
387
134
409
137
433
141
460
144
489
148
521
152
559
85 DB
72 WB
Low Side
High Side
130
346
131
361
134
380
136
401
139
423
142
448
146
476
149
506
153
539
157
578
Q30H3
75 DB
62 WB
Low Side
High Side
123
325
125
347
127
370
128
393
130
418
133
444
135
470
137
496
139
525
141
554
80 DB
67 WB
Low Side
High Side
132
333
134
256
136
379
137
403
139
429
142
455
144
482
146
509
149
538
151
568
85 DB
72 WB
Low Side
High Side
137
345
139
368
141
392
142
417
144
444
147
471
149
499
151
527
154
557
156
588
Q36H3
75 DB
62 WB
Low Side
High Side
127
343
129
363
131
383
133
406
135
429
137
453
138
480
140
507
142
536
145
566
80 DB
67 WB
Low Side
High Side
136
352
138
372
140
393
142
416
144
440
146
465
148
492
150
520
152
550
155
581
85 DB
72 WB
Low Side
High Side
141
364
143
385
145
407
147
431
149
455
151
481
153
509
155
538
157
569
160
601
Q43H3
75 DB
62 WB
Low Side
High Side
124
333
127
353
130
374
133
397
135
420
137
446
138
471
139
498
140
527
141
557
80 DB
67 WB
Low Side
High Side
133
342
136
362
139
384
142
407
144
431
146
457
148
483
149
511
150
541
151
571
85 DB
72 WB
Low Side
High Side
138
354
141
375
144
397
147
421
149
446
151
473
153
500
154
529
155
560
156
591
Q48H3
75 DB
62 WB
Low Side
High Side
120
337
122
362
123
385
125
410
128
436
130
461
132
488
134
515
137
542
138
570
80 DB
67 WB
Low Side
High Side
128
346
130
371
132
395
134
421
137
447
139
473
141
500
143
528
146
556
148
585
85 DB
72 WB
Low Side
High Side
132
358
135
384
137
409
139
436
142
463
144
490
146
518
148
546
151
575
153
605
Q60H3
75 DB
62 WB
Low Side
High Side
115
336
117
357
119
378
121
402
122
427
124
453
126
482
128
511
130
542
133
574
80 DB
67 WB
Low Side
High Side
123
345
125
366
127
388
129
412
131
438
133
465
135
494
137
524
139
556
142
589
85 DB
72 WB
Low Side
High Side
127
357
129
379
131
402
134
426
136
453
138
481
140
511
142
542
144
575
147
610
Low side pressure ± 4 psig
High side pressure ± 10 psig
Tables are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating charge being in the
system, the charge should be removed, system evacuated and recharged to serial plate instructions.
75°F outdoor temperature condenser fan motor is running on low speed.
TABLE 9
Cooling Pressure
(All Temperatures in Degrees F)